- 13 -
2.2.
Power supply Specifications
The following is the specifications for rated input voltage and power supply capacity for
each product.
Product
Input Power Supply
Current
Consumption
Power
Consumption
ETOS-100XP
AC 100V ~ 240V Free Voltage
(50/60Hz)
300mA or less
64VA
ETOS-150XP
300mA or less
64VA
ETOS-500XP
600mA or less
128VA
90 ~ 130 VDC
130W
2.3.
Battery Specification
The following is the standard for the battery information for each product. It is imperative
to read the precautions for battery use in the front of the manual before use.
The purpose of the battery is to save the log area and user memory data and to operate RTC.
It is not possible to charge the pertinent battery, therefore, it is imperative to replace it
in case of discharge.
** For purchasing a battery, contact our sales department.
2.3.1.
Battery Application Status and Parts by Product
Product
Application
Status
Battery
Name
Specification
Nominal
voltage /
current
Size (mm)
(height x diameter)
ETOS-100XP
O
XL-050F
Lithium
3.6V/1.2A
28 x 16.6
ETOS-150XP
O
XL-050F
Lithium
3.6V/1.2A
28 x 16.6
ETOS-500XP
O
XL-050F
Lithium
3.6V/1.2A
28 x 16.6
2.3.2.
Precautions for Use
(1) Do not charge, disassemble, heat, put into fire, short circuit, solder or give a shock to
the battery.
(2) Handling battery incorrectly may cause injury to the human body due to heat, breakage and
so on. There is a risk of fire.
2.3.3.
Battery Life
(1) It is possible to use the battery for at least 2 years by using it at room temperature
(based on 25 degree), but battery life depends on the power failure time and temperature
conditions.
(2) If the battery voltage drops below 1.5V, the system flag (SysBatteryLow) and log information
of the ETOS-RD can be used to check the battery voltage drop warning.
(3) If a warning for low battery voltage occurs, replace the battery as soon as possible for
operation.
(4) If the battery voltage becomes low, regular check and replacement management is required
because it can affect log data storage, user memory data storage, and RTC operation.
** When replacing the battery, it is recommended to replace the battery within 2 hours because
the internal supercap backup is possible only up to 2 hours.
** Before replacing the battery, please perform user memory and log backup.
** After purchasing, a warning occurs generally after about two years. But if the battery is