50
PROGRAMMING
T-SERIES
TRANSITION HUMIDITY SETTING
Customizes how the device will ramp up in levels
when triggered ON by humidity in AUTO MODE. Set a
transition threshold to determine how much the probe
humidity would need to surpass your trigger point for
the device to increase in level by one. The higher the
transition threshold figure is set to, the more the probe
humidity would need to surpass your set humidity
trigger for the level to increase. The lower the figure,
the less the probe humidity would need to surpass
your set humidity trigger for the level to increase. If the
figure is set to zero, it will jump to your maximum set
level without ramping when triggered ON.
Press the up or down button to cycle through 0% to
8% to set a transition threshold. The level will be set
one level above the OFF Mode level when the sensor
humidity first meets or exceeds the high humidity
trigger. For every transition threshold crossed, the
level will ramp up by one level, up until it reaches the
level set in ON Mode.
In this example, your high humidity trigger is set at
67%, the OFF Mode level is 2, and the ON Mode
level is 7. If the transition threshold is set to 0%, then
the devices will trigger to run at level 7 when the
sensor humidity meets or exceeds 67%. However,
if the transition threshold is set to 5%, then the fan
will trigger to run at level 3 when it meets or exceeds
67%. It will then step up to level 4 when meeting or
exceeding 72%, level 5 at 77%, and level 6 at 82%.
From 87% on, it will run at level 7, the level set in
ON Mode.