30
TRANSITION TEMPERATURE SETTING
In this setting, adjust the incremental rules in which
the fan speed ramps up or down for temperature
triggers in AUTO Mode. Press the up or down
button to cycle through 0°F to 8°F (or 0°C to 4°C)
to set a differential increment. Once setup, when
the sensor temperature first meets or exceeds
the high temperature trigger, the speed will start
at one speed above the speed set in OFF Mode.
Then for every differential increment that the sensor
temperature is different from the set temperature,
the speed of the fan will ramp up by one additional
speed level. This continues until the fan reaches the
speed set in ON Mode.
For example, let’s assume your high temperature
trigger is set at 80°F, the speed set in OFF Mode
is 0, and the speed set in ON Mode is 6. If the
differential increment was set to 0°F, then the fan
would have just triggered to run at speed 6 when
the sensor temperature meets or exceeds 80°F.
However, if the differential increment was set to 2°F.
Then the fan would start running at speed 1 when
it meets or exceeds 80°F. Then at speed 2 when
it meets or exceed 82°F. Then at speed 3 when it
meets or exceeds 84°F. Then at speed 4 when it
meets or exceed 86°F. Then at speed 5 when it
meets or exceed 88°F. Then from 90°F or higher, it
will run at speed 6 which was the speed set in ON
Mode.
PROGRAMMING
Содержание AC-CRT10
Страница 1: ...USER MANUAL USER MANUAL CLOUDRAY WHOLE HOUSE FAN SYSTEM ...
Страница 2: ......
Страница 39: ......
Страница 40: ...www acinfinity com ...