ASSEMBLY STEPS

Keep the head of expansion and the cone always clean  

and greased. If there is dust, dirt or debris, use a clean cloth 

 

that does not loose lint, then apply a thin layer of grease on it. 

Do not lubricate it too much.

Fully insert the fitting 

 

into the pipe. 

If you can not insert 

the fitting into the pipe, 

remove the fitting and 

expand once more. 

5

6

Screw in the expander head of the appropriate  

measure on the tool.

 

Insert the expander head 

 

into the pipe, then push the trigger; the expander 

head will expand and retract continuously while  

the trigger is pressed. Each time the segments  

retract, repeatedly and gently push the pipe inward 

on the expander head several times (*) until the pipe 

and ring are at level with the shoulder of the expan-

sion head. The expander head must not be pushed 

inwardly of the pipe so as not to block the move-

ment auto-rotation. Finally, remove the pipe when 

the segments retract and then release the trigger. 

Wipe off excess grease from inside the pipe.

4

www.ac-fix.com

The joint can be pressurized after 30 minutes with 

temperatures up to + 5 °. At lower temperatures, this 

time increases according to the table below. The 

maximum test pressure, which must not be excee-

ded, is 20 bar (2.0 MPa). At room temperature, after 

about 6 hours, the joint will be as strong as the tube.

(*) The approximate number of expansions depends on the diameter of the pipe:

 

16 x 1,8:  4  16 x 2,2:  6  

25 x 2,3:  8 

25 x 3,5:  20

 

20 x 1,9:  6  20 x 2,8:  12 

32 x 2,9:  12 

32 x 4,4:  

DO NOT USE

DO NOT USE WITH PIPES 32 x 4,4!

Intervals of 

 

temperatures

Time to 

 test pressure

+5ºC — +1ºC

1,5 hours

±0ºC — -4ºC

3 hours

-5ºC — -9ºC

4 hours

-10ºC — -15ºC

10 hours

Carry out the tightness test according to

test procedure A of the standard

UNE-CEN / TR 12108 IN: 2015

Leak test