15
6.3 DIP-switch
settings
CONFIG configuration Description
CONFIG: 1
(Default: OFF)
Defines the operation of the trouble output (TRBL).
ON: Switches in the event of battery faults (low
voltage or charging fault), input voltage or sounder
faults.
OFF: Switches only for battery faults (low voltage or
charging fault).
CONFIG: 2
(Default: OFF)
The OFF setting must not be changed!
CONFIG: 3
(Default: OFF)
Defines the maximum sounder duration.
ON: 5 minutes
OFF: 3 minutes
IMPORTANT:
The sounder activation always ends if there is no
longer a trigger signal at the C+/C- connectors!
CONFIG: 4
(Default: OFF)
Defines the sounder sound.
ON: Slow
OFF: Fast
Configuration ID1
Description
ID1: 1-3
(Default: All OFF)
Not used.
ID1: 4
(Default: OFF)
Selection of sounder signal according to French
Standard NFA2P.
ON: French Standard
OFF: Normal Standard