Charge

When this charging method is used, the output
values will be as follows:

Initial Charge Current . . . . . 0.30C Amps (max.)

Charge Voltage:

1st Stage . . . . . . . . .2.45V/cell (2.40 to 2.50
v/cell, max.)

2nd Stage . . . . . . . . 2.275V/cell(2.25 to 2.30
v/cell, max.)Switching Current From

1st Stage to 2nd Stage . . . . . . . . . . 0.05C Amps
(0.04C to 0.08C Amps)

Note: This charging method cannot be used in
applications where the load and the battery are
connected in parallel.

The C.V.C.C. is a fully regulated automatic charging
module designed for batteries. There are two 6 volt
versions available; one for standby applications and
the other for cyclic applications. Also there are two 1

2 volt versions available, again one for standby
applications and the other for cyclic applications.
When interfaced with the appropriate AC or DC
power supply, the C.V.C.C. guarantees safe charging
and maximum battery life. Figure 18 is a block
diagram of the C.V.C.C.

The C.V.C.C. modules are protected from both the
short circuiting of their D.C. output voltage and from
being reverse polarity connected to the battery.
Detailed specifications are available on request.

In designing a solar powered system, consideration
should be given to the fact that in addition to normal
periods of darkness, weather conditions may be such
that solar energy is limited, or virtually unavailable
for long periods of time. In extreme cases, a system
may have to operate for 10 to 20 days with little or no
power available for charging. Therefore, when
selecting the correct battery for a solar application,
the capacity should be determined based upon
maximum load conditions for the maximum period of
time the system may be expected to be without
adequate solar input.

In many instances the battery capacity will be 10 to
50 times greater than the maximum output of the
solar panels. Under these circumstances, the
maximum output of the solar array should be
dedicated to charging the battery with no load
sharing or intervening control devices of any kind.

Naturally, in cases where the output of the solar array
exceeds the capacity of the battery, and weather
conditions are such that the potential for
overcharging the battery exists, appropriate
regulated charging circuitry between the solar panels
and the battery is recommended.

Remote sites and other outdoor applications is where
most solar powered systems are to be normally found.
When designing a solar powered system for this class
of application, a great deal of consideration must be
given to environmental conditions. For example,
enclosures which may be used to house batteries and
other equipment may be subject to extremely high
internal temperatures when exposed to direct
sunlight. Under such conditions, insulating the
enclosure and/or treating the surface of the enclosure
with a highly reflective, heat resistive material is
highly recommended.

In general, when designing a solar powered system,
consultation with the manufacturers of both the solar
panel and the battery is strongly advised.

The charging voltage should be chosen according to
the type of service in which the battery will be used.
Generally, the following voltages are used:

For float (standby) use. . . . . .. 2.25 to 2.30 volts
per cell

For cyclic use . . . . 2.40 to 2.50 volts per cell

In a constant voltage charging system, a large amount of
current will flow during the initial stage of charging but will
decrease as the charging progresses. When charging at
2.275 volts per cell, the current at the final stage of
charging will drop typically to a value of between 0.0005C
Amps and 0.004C Amps. When a battery has been charged
up to a level of 100% of the discharged ampere hours, the
electrical energy stored and available for discharge will be
90% or more, of the energy applied during charging.
Charging voltage should be regulated in relation to

C.V.C.C. CONSTANT VOLTAGE, CONSTANT
CURRENT CHARGE MODULE

Charging Voltage

Solar Powered Chargers

A battery is an indispensable component of any solar
powered system designed for demand energy use. Since
solar cells have inherent constant voltage
characteristics, Powerline SC can be charged directly
from the solar array using a simple diode regulated
circuit as shown in Figure 19.

Figure 19. BLOCK DIAGRAM OF A

SOLAR POWERED CHARGING SYSTEM

SOLAR CELL
OR PANEL

LOAD

BATTERY

Figure 18. Block diagram of C.V.C.C.

C.V.C.C.

CHARGE UNIT

WHITE
WHITE
BLUE
GREEN

BLUE
YELLOW
BLACK

RED

LED
LED
LED
LED

+




{

Input

Input Indicator

Charge Indicator

DC Output

+

+

Содержание Powerline SC Series

Страница 1: ...SC Powerline Series Product Guide SEALED LEAD ACID BATTERY VALVE REGULATED Standard Commercial ...

Страница 2: ...oduction 01 Technical Features 01 Applications Construction 02 General Specifications 03 Discharge 05 Charge 07 11 12 02 Expected Service Life of Powerline SC Design Application Suggestions to Ensure Maximum Service ...

Страница 3: ...eration of Powerline SC in any orientation excluding continuous inverted use without loss of capacity service life or leakage of electrolyte The Powerline SC also conforms to IEC 60896 21 22 2004 Powerline SC are equipped with a safe low pressure venting system which is designed to release excess gas and close automatically as the internal gas pressure rising to an unacceptable level This low pres...

Страница 4: ...ommunications Equipment Computers Control Equipment Electronic Cash Registers Electronic Test Equipment Emergency Lighting Systems Fire Security Systems Geophysical Equipment Medical Equipment Microprocessor Based Office machines Solar Powered Systems Telecommunication Systems Television Video Recorders UPS EPS Vending Machines l l l l l l l l l l l l l l l l l Applications ...

Страница 5: ...51 151 151 151 151 181 50 65 65 65 98 76 94 93 93 93 94 166 100 98 98 98 100 166 1 80 2 40 2 58 2 58 3 57 5 80 84 49 52 56 84 126 240 140 150 160 240 360 9 5 22 20 20 16 14 F1 or F2 F1 or F2 F1 or F2 F1 or F2 F1 or F2 M5 x Ø12 A D D D D B Certification l l l l l CE UL ISO9001 ISO14001 OHSAS18001 l GOST Terminals Terminal Layout F1 F2 M5x 12 φ A B D 4 80 6 35 3 25 6 35 7 95 4 25 0 80 M5 φ12 0 80 ...

Страница 6: ...xample if a lead acid battery were discharged to zero volts and left standing in either on or off load conditions for a long period of time severe sulphation would occur raising the internal resistance of the battery abnormally high In such an extreme case the battery may not accept charge Powerline SC have been designed to withstand some levels of over discharge However whilst this is not the rec...

Страница 7: ...arious temperatures Available capacity measured by open circuit voltage Figure 4 shows extrapolated service life condition for powerline sc at different ambient temperatures As can be seen from figure 4 higher ambient temperatures will reduce service life Impedance figure 4 Temperature Life characteristics of powerline SC The internal resistance impedance of a battery is lowest when the battery is...

Страница 8: ... 120 100 80 60 40 20 0 0 02 0 08 0 1 0 5 10 15 20 25 30 35 40 11 0 12 0 13 0 14 0 4 50 4 00 3 50 0 V 0 04 0 06 7 50 7 00 6 50 6 00 5 50 140 120 100 80 60 40 20 0 5 00 4 50 4 00 3 50 0 2 4 6 8 10 12 14 16 18 20 CHARGE VOLTAGE CHARGED VOLUME AFTER 50 DISCHARGE AFTER 100 DISCHARGE CHARGING TIME HOURS 7 50 7 00 6 50 6 00 5 50 CHARGING CURRENT 11 0 12 0 13 0 14 0 15 0 V 0 1CA 7 20V 14 4V 4 8V CONSTANT ...

Страница 9: ...ll is applied occurs after the battery has recovered about 80 of its rated capacity This is one of the most efficient charging methods available as the recharge time is minimized during the initial stage whilst the battery is protected from overcharge by the system switching to stage 2 float standby charge at the switching point Y POWERLINE SC SERIES 07 Charge Figure 15 Characteristics of two SC12...

Страница 10: ... the potential for overcharging the battery exists appropriate regulated charging circuitry between the solar panels and the battery is recommended Remote sites and other outdoor applications is where most solar powered systems are to be normally found When designing a solar powered system for this class of application a great deal of consideration must be given to environmental conditions For exa...

Страница 11: ... LOAD condition may result in undercharging The constant voltage range required by a battery is always defined as the voltage range applied to a battery which is fully charged Therefore a charger having the output characteristics illustrated in Figure 22 should be adjusted with the output voltage based on point A The most important factor in adjusting charger output voltage is the accuracy at poin...

Страница 12: ... speaking the most important factor is depth of discharge Figure 26 illustrates the effects of depth of discharge on cyclic life The relationship between the number of cycles which can be expected and the depth of discharge is readily apparent If an extended cycle life is required then it is common practice to select a battery with a larger capacity than the one that is required to carry the load ...

Страница 13: ...duce electrical discharges in the form of sparks 3 When the battery is operated in a confined space adequate ventilation should be provided 4 The battery case is manufactured from high impact ABS plastic resin It should not be placed in an atmosphere of or in contact with organic solvents or adhesive materials 5 Correct terminals should be used on battery connecting wires Soldering is not recommen...

Страница 14: ...n fresh water and seek IMMEDIATE medical attention 14 DO NOT INCINERATE batteries as they are liable to rupture if placed into a fire Batteries that have reached the end of their service life can be returned to us for safe disposal 15 Touching electrically conductive parts might result in an electric shock Be sure to wear rubber gloves before inspection or maintenance work 16 The use of mixed batt...

Страница 15: ...sun com Email sales abtbatt com Our sales growth is due to a complete Global Network with Master distributors and Country managers who apply ABT commercial strategy and through Global Key Account in ABT World Wide ABT VRLA Battery PowerLine Thunder Enduro Sunwind e Trek ABT Copyright 2010 Shandong Sacred Sun Power Sources Co Ltd All rights reserved Version 201105 ...

Отзывы: