background image

AC to DC Transmitters, Isolated, Field Rangeable 

APD 6380

Input:

 

True RMS 0-40 mVAC to 0-300 VAC, 0-4 mAAC to 0-200 mAAC

Output:

 

0-1 V to 0-10 VDC, ±5 VDC, ±10 VDC, 0-2 mA to 20 mADC

 

O

One Minute Setup for Hundreds of I/O Ranges

 

O

External Switches & Tables for Range Selection

 

O

Zero and Span Output Calibration Potentiometers

 

O

Full 1200 V Input/Output/Power Isolation

 

O

Input and Output LoopTracker

®

 LEDs

 

O

Output Test Button

 

O

Built-In Loop Power Supply for Sink/Source Output

 

Q

Convert, Boost, and Rescale Process Signals

 

Q

Isolate Single-Ended (Common Ground) PLC Inputs

 

Q

Interface Process Signals with Panel Meters, PLCs, 
Recorders, Data Acquisition, DCS, & SCADA Systems

Applications

Options–add to end of model number
M01

 

Output reversal, such as 20-4 mA output 

U

 

Conformal coating for moisture resistance

Accessory—order as separate line item
API BP4

  Spare removable 4 terminal plug, black

Model

Input

Output

Power

APD 6380

Field configurable—specify range if 

factory is to set switches

Field configurable—specify range if 

factory is to set switches

85-265 VAC or 60-300 VDC

APD 6380 D

9-30 VDC or 10-32 VAC

Description

The APD 6380 accepts an AC voltage or current input and 
provides an optically isolated DC voltage or current output that 
is linearly related to the input. 
Typical applications include signal isolation, conversion, boost-
ing or a combination of the three. Full 3-way isolation (input, 
output, power) makes this module useful for ground loop 
elimination, common mode signal rejection or noise pickup 
reduction.

Sink/Source Output Versatility

For maximum versatility a milliamp output can be selectively 
wired for sinking or sourcing. This allows the APD 6380 mil-
liamp output to connect to  a powered or unpowered current 
loop. The 20 VDC output loop supply can be used to power a 
passive mA device if required. 

LoopTracker 

API exclusive features include two LoopTracker LEDs (green for 
input, red for output) that vary in intensity with changes in the 
process input and output signals. These provide a quick visual 
picture of your process loop at all times and can greatly aid in 
saving time during initial startup and/or troubleshooting. 

Output Test 

An API exclusive feature includes the test button to provide a 
fixed output (independent of the input) when held depressed. 
The test output level is potentiometer adjustable from 0 to 
100% of output span. 
The output test button greatly aids in saving time during initial 
startup and/or troubleshooting.

All models are field rangeable 

For APD 6380, specify if UL version is required 
Order options and accessories as required 
Order D versions for operation on low voltage power

How to Order

Free factory setup. Please specify on your order 

Input range 
Output range

AC Input Ranges

Field selectable ranges via switch settings
Voltage: 

0-40 mVAC to 0-300 VAC 

Current: 

0-4 mAAC to 0-200 mAAC 

Measurements are true RMS

Input Impedance

Voltage (0-4 VAC):  1 M

 minimum 

Voltage (>4 VAC):  220 k

 minimum 

Current: 10 

 typical

Input Frequency

40 Hz to 1000 Hz sinusoidal

Common Mode Rejection

120 dB minimum

LoopTracker

Variable brightness LEDs indicate I/O loop level and status

DC Output Ranges

Field selectable ranges via switch settings
Voltage: 

0-1 VDC to 0-10 VDC, 10 mA max 

Bipolar voltage:  ±1 VDC to ±10 VDC 
Current: 

0-2 mADC to 0-20 mADC 

 

20 V compliance, 1000 

 at 20 mA 

Output offset: 

±100% in 15% increments

Output Calibration

Multi-turn zero and span potentiometers  
±15% of span adjustment range typical

Output Loop Power Supply

20 VDC nominal, regulated, 25 mADC 
Max. ripple, less than 10 mV

RMS

May be selectively wired for sinking or sourcing mA output

Output Test

Front momentary button sets output to test level 
Potentiometer adjustable 0-100% of span

Output Ripple and Noise

Less than 10 mV

RMS

 ripple and noise

Linearity

Better than ±0.1% of span

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient 

Better than ±0.02% of span per °C stability

Response Time

200 milliseconds nominal (0-90%)

Isolation

1200 V

RMS

 minimum 

Full isolation: power to input, power to output, input to output

Power

85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum 
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum

Housing and Connectors

IP 40, requires installation in panel or enclosure 
For use in Pollution Degree 2 Environment 
Mount vertically to a 35 mm DIN rail 
Four 4-terminal removable connectors, 14 AWG max wire size

Dimensions

0.89" W x 4.62" H x 4.81" D   
22.5 mm W x 117 mm H x 122 mm D  
Height includes connectors

Connect mA Output 

for Sink or Source

Output LoopTracker 

LED

Input LoopTracker 

LED

Adjustable Output 

Test Function

Hundreds of Range 

Selections

Adjustable Output 

Offset

Universal 

Power

Zero and Span for 

Output

Removable Plugs

© 11-19

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

A

BSOLUTE

BSOLUTE

 P

 P

ROCESS

ROCESS

 I

 I

NSTRUMENTS

NSTRUMENTS

1  2  3  4

5  6  7  8

9 10 11 12

13 14 15 16

See Wiring 

Diagrams on 

Page 3

Quick Link: 

api-usa.com/6380

Minute 

Setup!

1

Free Factory 

I/O Setup!

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

Made in USA

File E145968

85-265 VAC, 60-300 VDC 

model only

Applications Link 

api-usa.com/apps

Pb

Lead 

Free

Содержание APD 6380

Страница 1: ... For APD 6380 specify if UL version is required Order options and accessories as required Order D versions for operation on low voltage power How to Order Free factory setup Please specify on your order Input range Output range AC Input Ranges Field selectable ranges via switch settings Voltage 0 40 mVAC to 0 300 VAC Current 0 4 mAAC to 0 200 mAAC Measurements are true RMS Input Impedance Voltage ...

Страница 2: ... VE38V VE31V VE36V VE39V VE32V VE37V VE33V VE34V VE35V VE30I VE38I VE31I VE36I VE39I VE32I VE37I VE33I 0 20 V VF20V VF28V VF21V VF26V VF29V VF22V VF27V VF23V VF24V VF25V VF20I VF28I VF21I VF26I VF29I VF22I VF27I VF23I 0 25 V VC20V VC28V VC21V VC26V VC29V VC22V VC27V VC23V VC24V VC25V VC20I VC28I VC21I VC26I VC29I VC22I VC27I VC23I 0 40 V V460V V468V V461V V466V V469V V462V V467V V463V V464V V465V ...

Страница 3: ... generally easier to select ranges before installation The module side label lists common ranges See the model serial number label for module information options or if a custom range was specified It may also be possible to use the next highest setting and trim the output signal with the zero and span potentiometers Switch A Set to V for voltage input Switch B Input range Switch C Input range Swit...

Страница 4: ... that can be used as a diagnostic aid during initial start up or troubleshooting When released the output will return to normal The Test Cal potentiometer is factory set to approximately 50 output It can be adjusted to set the test output from 0 to 100 of the output span Press and hold the Test button and adjust the Test Cal potentiometer for the desired output level Operation The APD 6380 accepts...

Отзывы: