Only open inlet posts that are to be used. Saw off as little as possible so that as much material as possible is
left for the plug connection.
File down sharp edge inside and outside.
ATTENTION
The pump connection ports should not be used as inflow ports. Connect a maximum
of 2 submersible pumps per tank.
1034-00
Figure 5 Opening the connections on the collection tank
4.4
D���h����� L���
The discharge line must be installed in compliance with the relevant regulations.
DIN 1986/100 and EN 12056 applies in particular to the following:
The discharge line should be fitted with a backwash loop (180° bend) located above the backwash level and
should then flow by gravity into the collection line or sewer.
The discharge line should not be connected to a down pipe.
No other inflows or discharge lines should be connected to this discharge line.
ATTENTION
The discharge line should be installed so that it is not affected by frost.
The vent line is connected by means of a push-on sleeve to the vertical outlet at the top of the collection tank.
It should be of constant cross-section (min. DN 70) and should have a continuous rise to above roof level.
-
-
-