Installation and Operating Instructions 

3

ABS Control panel CP114

GB 0825-A

Options

Backup-battery 12 V; 1,2 Ah (part-no. 6216 0961)
It is possible to operate parts of the PC111 unit  independent of mains. An integrated charger functions as a 

FRQVWDQWEXIIHUIRUWKHEDWWHU\0RUHLQIRUPDWLRQVHHPDQXDORIWKH3&7KHUHWUR¿WEDFNXSNLWLQFOXGHV
9OHDGDFLGEDWWHU\$K¿[EUDFNHWZLULQJNLWDQGLQVWDOODWLRQJXLGH

Thermostatic controlled heater 230 V, 10 W (part-no. 6216 0088)
If unfavourable mounting is necessary e.g. outdoor installation, a thermostatic heater can be installed inside of 

WKHVWHHOFDELQHW$UHWUR¿WNLWLQFOXGHVWKHUPRVWDWƒƒKHDWHU:IXVH$ZLULQJNLWDQGLQVWDOODWLRQ

guide.

External alarm unit (audio-visual) 12 VDC (part-no.: 6216 0978)
The external alarm unit combines a 12 VDC LED-alarm light and a piezo-buzzer IP65, mounted in plastic box
IP66.

All fundamental settings and operating steps are described in the standard manual of the PC111 (part-no. 

$WKH\UHPDLQYDOLG$GGLWLRQDOO\\RXZLOO¿QGWKHIROORZLQJSDUDPHWHUVLQWKHVWDUWPHQXRSWLRQ
¿JXUH

Menu item

Value

Comment

Stop criteria

6WRSÀRDW

VWRSFULWHULDXVLQJÀRDWV

New Functions

Ľ

Relay 2 function

[Reversing pump, Start Cap., Off]

Reversing if fault. Activated by output 
LO1 from VFD.

Rev. Delay time

Minutes

Delay reverse function, so that the 
pump can stop.

Rev. Run time

Seconds

Running time in changed direction.

Max. no Attempts

1 - 3

After reversion the pump starts. Pro-
cedure is considered as successful if 
at least the running time of the “Rev.
delay” is reached.

After that the counter will be reset. If
fault occurs again, next start attempt,
max. 3 attempts possible. All further 
attempts stop the pump, created alarm 
have to be reset manually.

P1 Rel. when Rev.

ON - OFF

Function of relay 1 during reversion of 
rotation (

MUST BE

 in position „OFF“).

Curr. Sensor P1

ON - OFF

Position „OFF“. Current measuring 
occurs via VFD.