D - Installation Examples 

 

1.

 

Single AC Powered Sensor 

The following example shows an AC powered sensor (ABM400 or ABM430 series), without a current output 
connection, connected to a Gateway. 

As the current loop output of the sensor is unused, the Gateway, located within 6ft (2m), is shown directly wired to the 
sensor through one cable gland, while the AC supply requires a second separate cable gland. 

As the Gateway is not supplying sensor power, the red wire is either cut off or insulated with tape inside the sensor. 
The black wire from the red/black pair is still connected to provide a signal common for the RS485 link, so it is 
connected to Common at Terminal #4 (mA Output “-“). 

The shield is shown grounded at the power supply and not connected in the sensor. As AC powered sensors have both 
Terminals 3 and 6 earth-grounded for electrical safety, the shield could instead have been left unconnected at the 
power supply and connected to Terminal 3 in the sensor. 
 

 

Figure 1 – AC Supply Sensor Connections (No Current Output) Using Gateway Pigtail 

 
 

 

Содержание ABM1-RUCM-C4

Страница 1: ... it is highly recommended that the installer determine an optimal mounting location by using a cell phone display to assess the signal strength The standard antenna supplied with the Gateway has a magnetic base and a 6 2m cable that allows mounting on top of a tank or structure for optimal signal strength while mounting the Gateway in a more sheltered or accessible area The optional SMA mounted an...

Страница 2: ...on box is required to connect it to the RS485 and DC power buses It is not necessary to install the Gateway at one end of the RS485 bus as shown in several examples in Section D it can be located anywhere in the network The RS485 cabling must be connected in a multi drop or daisy chain configuration as star configurations i e with long branches are not recommended Short stubs are acceptable maximu...

Страница 3: ...y grounded through their mounting for instance where a metal or otherwise conductive tank is grounded to earth through its base and the sensor is installed without an isolating mount such as an aiming device If a DC sensor is not indirectly grounded in this manner nor grounded through an earth ground wire connected to either Terminal 3 or 6 then the system shield wire should be connected to Termin...

Страница 4: ...Gateway is not supplying sensor power the red wire is either cut off or insulated with tape inside the sensor The black wire from the red black pair is still connected to provide a signal common for the RS485 link so it is connected to Common at Terminal 4 mA Output The shield is shown grounded at the power supply and not connected in the sensor As AC powered sensors have both Terminals 3 and 6 ea...

Страница 5: ... shown being earth grounded at the sensor since being AC powered Terminal 3 must be earthed through Terminal 6 Optionally the shield could be earth grounded at the junction box but not at the sensor As Terminal 4 mA Output is the signal common for both the current output and the RS485 in the sensor it is acceptable to provide this connection through the one black wire to the junction box as shown ...

Страница 6: ... the sensor is mounted on a non metallic tank or uses a sensor aiming mount that electrically insulates the housing from earth ground Figure 3 Simple DC Sensor Connections No Current Output Note that if the DC power supply is located at a significant distance and the junction box has an available earth ground connection much closer to the Gateway and sensor it may be more desirable to ground the s...

Страница 7: ...uirements see section B Requirements Power Supply above Figure 4 Multiple DC Sensor Connections Shield Earth Grounded at Power Supply 5 Multiple DC Powered Sensors The following example shows the Gateway wired to control multiple sensors each with a current loop output to the PLC As they are all DC version sensors they are powered directly from the 24Vdc supply It is shown as a separate power supp...

Страница 8: ...REV 0 0 April 18 2023 Page 8 Figure 5 Multiple DC Sensors with Current Outputs ...

Страница 9: ... be indirectly earth grounded through its mounting configuration caution required re shield wire may be powered from the Gateway sensor power output AC Radar ABM400 xxxYYC4 series and ABM430 xxxYYC4 series should be earth grounded through its AC supply do not connect shield wire cannot be powered from the Gateway where YY any one of R2 R5 R6 R2R7 or R6R2 ...

Отзывы: