CONTROL POINTS

BD

LJ,

Li

BS

Q)~

88

~

l

l

The operator

drives the door against the closed position for a

preset value of 1 second.

Fire doors - adjust the lock control relay hold time to a minimum.

Sequencing

1

=

Opening and closing sequencing

for pair of rebated doors

The master door opens first and then the slave.
The slave door closes first and then master door.
All impulses are connetcted

to the master.

2

=

Sequential

opening (stepwise

opening)

Used in two doors following

each other. The first door opens

from impulse and commands

the second door to open.

The opening delay of the second door is adjusted in control

point 4. Note! The inside impulse connection

is not operational.

3

=

Interlock

controlled

doors

Used in two door following

each other. The first door opens

from impulse and the second door opens from impulse after
the first door Is fully closed.

The bolt information

is needed in connectors

10 and 11.

MASTER

Master operator

for double doors

o

=

No operation/slave

operator

1

=

Master operator

=

l

Function of impulse

0=

Normal

1

=

The first impulse opens the door,
second closes the door
The operator

holds the door open until hold open time

expires or there is a closing impulse. Note! If hold open
time is set to 60 seconds, the operator

remains open

until the second impulse is activated.

15

Содержание DA400

Страница 1: ..._ _ ABLOY ABlOyID DA400 Swing door operator _ _ OJ f I I I I I I I y l I I I _V __ ER_SIO_N_1 _5 _ 0 All ASSA A810Y Group co y...

Страница 2: ...res running to the switch carries 5 V and the other the ground level of the control unit when the switch is open 1 Sequencing 2 1 sequence control 7 2 d 2 Outside impulse inhiblV 2 3 Main power state...

Страница 3: ...iately on a impulse The contacts of a impulse device must be potentialily free and have a normally open function 5 Inside impulse The door opens after preset delay 0 15 sec 6 Safety sensor The sensor...

Страница 4: ...using separate program switch LEO X4 EJ Pulse counter 27 I red 26 I loci 25 24 k 23 I 22 I leek 21 I red 20 lId 19 CONTROL UNIT Permanent wiring shall be employed if required by local codes Permanent...

Страница 5: ...ter has three sensors Two count the pulses and the disk direction the other senses the perimeter of the disk n Adjusting the door closed position 1 Mount the operator and fit the arm When closing the...

Страница 6: ...selector e g 0 MANUAL 1 AUTOor 2 OPEN The right hand display section indicates the status of opening pulses the safety sensor and the locking circuit Program selector I pulse display status I ro C Ix...

Страница 7: ...Adjustment button When the desired control point has been selected with the Selection button pressing the Adjustment button validates the control value and flashes on the display The Adjustment LEDwil...

Страница 8: ...speed 40 _ _ _ _ n 1 3 60 Door open position 48 1 __ _ _ _ I C 0 60 ClosIng direction Starting point of final speed 10 1 __ _ _ J 1 10 Operator s force Sealed 5 L c _ _ _ _ _ LI 0 15 Delay time for i...

Страница 9: ...__ _ D 8J 1 or 0 Operation of lock control relay a _ _ DB 1 or 0 Closing direction Safety feature a I I B jJ 0 10 Hold open force a _ _ 8fl 0 10 Pressure closed before opening a JLJ laB _ _ f 1 10 Lo...

Страница 10: ...iately but the door is delayed I LJ 0 in opening to accommodate for the locks release 0 I CJN CJ Adjust the opening speed so that the safety feature is not activated Adjust the final speed in order so...

Страница 11: ...o close the door at intervals of 60 seconds 8 corresponds to minimum sensitivity 1 on 0 off Power assisted manual opening will function when the door operator is set to automatic mode DB 1 Standard ar...

Страница 12: ...open The opening delay of the second door is adjusted in control point 4 Note The inside impulse connection is not operational 3 Interlock controlled doors Used in two door following each other The fi...

Страница 13: ...e counter indicates number of openings The fixed obsticles in safety sensor zone can be excluded by adjusting the area smaller than the door open position Dlspalys the program version 0 DA400 Europe 1...

Страница 14: ...y is connected put the battery operation ON If battery operation Is not selected the battery will not be charged Adding batteries Fire door use DA131 1 pes 12V 2 2Ah battery adapter Full battery back...

Страница 15: ...hould be replaced The test made by the operator The battery is loaded with 0 4 A test load for a 30 second period If the battery voltage drops under U S V the battery is found unsuitable a red LEDflas...

Страница 16: ...In 24 hour period the battery should be replaced The test made by the operator The battery is loaded with 0 4 A test load for a 30 second period If the battery voltage drops under 11 5 V the battery i...

Страница 17: ...t made by the operator The battery is loaded with 0 8 A test load for a 10 second period If the battery voltage drops under 23 V the battery is found unsuitable a red LEDflashes at the end of the oper...

Страница 18: ...on 1 2 3 4 FUlEDETECTOR N C iN O relay output Fire detector input If the jumper is on the adapter requires N O output from the fire detector otherwise N e Battery alarm keep If the jumper is on the ba...

Отзывы: