UPS parameters which can be modified by the user from the control panel are listed
in the table below.
Parameters
Content
Range
Default
Battery
Independent/Common
Ind. / Common
Common
Total cell number
192 ~ 240
240
Capacity
1~1000
18
(1)
Voltage Temparature compensation Yes / No
No
Detect the Battery connecting
Yes / No
Yes
Charger current
0.0~1.0
0.1
CV Charger voltage [V/cell]
2.000~2.550
2.300
FV Charger voltage [V/cell]
2.000~2.550
2.250
Low battery voltage [V/cell]
1.850 ~ 1.883
1.850
Weak battery voltage [V/cell]
1.600 ~ 1.800
1.600
Battery test 2 minutes
Yes / No
Yes
Output
Output voltage
220
、
230
、
240
230
Output frequency
50
、
60
50
Fine adjustment voltage
-8 ~ 8
0
Transformer
Input transformer
No / Mains & Bypass
No
Input transformer ratio
(2)
0.00~10.00
0
Output transformer
No / Yes
No
Output transformer ratio
(2)
0.00~10.00
0
Other
Unit number
1 ~ 6
1
Number of units in parallel system
1 ~ 6
1
Set EPO logic
NO/NC
NO
(1)
The default setting from 10kVA to 40kVA is 18 AH and 60kVA is 88AH.
(2)
Transformer ratios can be calculated as following,
(3)
Input transformer ratio = Vp_in/Vs_in; Output transformer ratio = Vs_out/Vp_out
UPS
Vp_in
Vs_in
Vp_out
Vs_out
Input
Transformer
Output
Transformer
52
192321262008007
Содержание TAURUS 10 kVA
Страница 1: ...TAURUS Series 10 80 kVA UPS Installation and Operation Manual...
Страница 7: ...10 20kVA Right Side View 1 A 1E Through Hole for Parallel Communication Cable 5 192321262008007...
Страница 10: ...30 40kVA Right Side View 1 A 1E Through Hole for Parallel Communication Cable 8 192321262008007...
Страница 23: ...Floor Fixing for 60 80kVA Stationary Type Without Wheel 21 192321262008007...
Страница 32: ...UPS in parallel use separate battery Load 3P N UPS in parallel use common battery Load 3P N 30 192321262008007...
Страница 35: ...2 5 Communication Cables Connections 10 20kVA 30 40kVA 60 80kVA 33 192321262008007...