2.6
UPS Parallel Connections
The UPS can be operated in parallel for extend the capacity and enhances system
reliability.
Up to 6 UPS units can be operatedin parallel.
The size and length of the input and output cables must be identical for all UPS units.
The phase rotation must be the same for each UPS unit.
It is recommended to use an external bypass cabinet to facilitate maintenance and
system testing for parallel operation system.
Parallel configuration must be performed by authorized and qualified technicians who
are familiar with this UPS.
Parallel communication cables are requested to connect to UPS each other.
Please only use the parallel communication cables which are supplied with UPS
manufacturer for ensure UPS can operate correctly in a parallel configuration.
The parallel communication cables must be connected in a ring topology, and the
maximum total length of the parallel communication cables must be less than 38
meters.To ensure good communication quality you must set the Switch & SW3 of the
two farthest UPS to the “ON” position as shown in below.
37
192321262008007
Содержание TAURUS 10 kVA
Страница 1: ...TAURUS Series 10 80 kVA UPS Installation and Operation Manual...
Страница 7: ...10 20kVA Right Side View 1 A 1E Through Hole for Parallel Communication Cable 5 192321262008007...
Страница 10: ...30 40kVA Right Side View 1 A 1E Through Hole for Parallel Communication Cable 8 192321262008007...
Страница 23: ...Floor Fixing for 60 80kVA Stationary Type Without Wheel 21 192321262008007...
Страница 32: ...UPS in parallel use separate battery Load 3P N UPS in parallel use common battery Load 3P N 30 192321262008007...
Страница 35: ...2 5 Communication Cables Connections 10 20kVA 30 40kVA 60 80kVA 33 192321262008007...