Operation Procedure:
Make sure that you may switch the modes according to the following procedure:
1.
UPS MODE
=>
UTILITY MODE(Maintenance bypass)
Step 1: Make sure the orange lamp is lit. If not, please refer to Trouble
Shooting.
Step 2: Switch the CAM Switch (Maintenance Bypass Switch) from UPS to
Utility.
Step 3: Turn off the UPS.
Step 4: Remove the connection between the UPS and the MTBS.
Step 5: Your maintenance or replacement of the UPS may be proceeded.
2.
UTILITY MODE(Maintenance bypass)
=>
UPS MODE
Step 1: Connect the input and output of the UPS to the MTBS, then turn on the
UPS in accordance with the operation manual of the UPS.
Step 2: Make sure if the Green lamp of the UPS is lit. If not, please refer to
the Trouble Shooting.
Step 3: Switch the CAM Switch (Maintenance Bypass Switch) from Utility to
UPS, then the load connected will be supplied by the UPS now.