Cabinet and related mounting accessories
The UPS should be placed inside a cabinet to prevent unexpected hazards.
We have designed rack and mounting accessories for the BRIC30S/BRIC30N as
an option for our customers to choose from. Detailed installation instructions are
provided separately.
9.2.2.
SNMP Network Card
If the user wishes to monitor the UPS in real-time over the network, the
TCP/IP network card is available as an option. The network card requires a
dedicated monitoring platform. Instructions are provided separately.
9.2.3.
Dry Contact Card
The dry contact card is a programmable circuit that can be programmed and
configured to suit the user's needs before shipping. Instructions are provided
separately.
41
10.
Specification
Item
Specifications
General
Nominal power
30kVA/27kW
Power scalable (parallel operation)
Up to 4 units for 120kVA or 90kVA + 30kVA redundancy
Operational modes
VFI, ECO, Converter
Display and MMI
4.3'' touch screen
Built-in communication port
RS232 & RS485
External communication slot
2 cards work simultaneously
Audible noise
< 60dBA at 1 meter
Working temperature
0~40 degree C
Working humidity
0~95%
Tested to standards
Safety: IEC/EN 62040-1,
EMC: EN 62040-2
Mark
CE
Overall Dimensions (WxDxH)mm
440 x 430 x 800
Net Weight (kg)
78
Input electrical characteristics
Technology
Bridge with IGBT
Nominal mains supply voltage
N
+20% ~ -20% with 100% of the nominal power
-20% ~ -40% with 50% of the nominal power
Voltage tolerance
< -40% changing to backup mode
Nominal frequency
50/60Hz (auto sensing)
Frequency tolerance
±5Hz
Power factor
≥ 0.99 at full load and nominal voltage
Current harmonic distortion (THDi)
< 3% at full load and nominal voltage
Max inrush current at start-up
< 45A (no over-current)