4.2. Fault LED Lights up and No Output
4.2.1. Troubleshooting
FIG. 4.2
Check Items
Trouble-shooting
Output Short Circuit
Check if the output end of the UPS is in short
circuit.
Overload(>120%)
Reduce the output load.
MS1K/MS1KR: 1000VA/700W
Battery voltage is abnormal
1. If the battery voltage is under 28.8V, replace the batteries
。
2. Remove the battery, check the charge voltage. If the voltage
is over 43V, the charger circuit is out of order. Refer to fig4.1,
please check U14
、
U10
、
VR1 and other device nearby.
INVERTER Voltage ERROR
Refer to fig.4-4, Check U7
、
U8
、
Q13
、
Q14
。
The Fan on the rear panel is out of
order
1. Check to see if the connection to the fan is
Properly done.