14)
Tone Selection and 2nd and 3rd Stage Alarms
The BExS120D and BExS110D sounders have 32 different
tones that can be selected for the first stage alarm. The
sounders can then be switched to sound second and third
stage alarm tones. The tones are selected by operation of a
DIP switch on the pcb for both DC and AC units. The tone
table on page four shows the switch positions for the 32
tones and which tones are available for the second and third
stages. To operate the sounder on stage one simply connect
the supply voltage to the normal supply terminals (+ve and –
ve for DC units, L and N for AC units).
The operation of the second and third stages is different for
DC and AC units.
DC Units Second and Third Stage Tone Selection
The BExS120D and BEx110D DC sounders have the facility
to use ve or –ve switching to change the tone to the
second and third stages. For –ve switching connect the two
headers on the pcb to the left-hand (marked –ve) and centre
pins. For +ve switching connect the headers to the right hand
(ve) and the centre pins. To change to the second
stage tone, connect either a -ve or +ve supply line to terminal
S2, depending on which switching mode is being used while
maintaining the dc supply to the +ve and –ve terminals.
Similarly for the third stage tone, connect a -ve or +ve supply
line to terminal S3. The supply to the S3 terminal will
automatically override a supply to the S2 terminal.
AC Units Second and Third Stage Tone Selection
To select the second and third stage tones on the BExS120D
and BExS110D AC sounders the Common (C) terminal on
the three way terminal block on the pcb is connected to the
S2 terminal for the second stage tone and the S3 terminal for
the third stage tone.
15)
Volume Control
All BExS120D and BExS110D sounders, with the exception
of 12V DC units, have a volume control to adjust the output
level.
To
set
the
required
output
level,
adjust
the
potentiometer on the pcb. For maximum output level the
potentiometer should be set to the fully clockwise position.
16)
End of Line Monitoring (DC Units)
On BExS120D and BExS110D DC units, dc reverse line
monitoring can be used if required. All DC sounders have a
blocking diode fitted in their supply input lines. An end of line
monitoring diode or an end of line monitoring resistor can be
connected across the +ve and –ve terminals. If an end of line
resistor is used it must have a minimum resistance value of
3k3 ohms and a minimum wattage of 0.5 watts or a minimum
resistance value of 500 ohms and a min. wattage of 2 watts.
TONE SELECTION TABLE
Tone Selection
DIP Switch
Settings
Stage Selection
Stage 1
Frequency Description
1 2 3 4 5
Stage 2
Stage 3
1
Continuous 1000Hz
Toxic Gas Alarm
0 0 0 0 0
Tone 31
Tone 11
2
Alternating 800/1000Hz at 0.25s
intervals
1 0 0 0 0
Tone 17
Tone 5
3
Slow Whoop 500/1200Hz at 0.3Hz
with 0.5s gap repeated
0 1 0 0 0
Tone 2
Tone 5
4
Sweeping 800/1000 at 1Hz
1 1 0 0 0
Tone 6
Tone 5
5
Continuous at 2400Hz
0 0 1 0 0
Tone 3
Tone 27
6
Sweeping 2400/2900Hz at 7Hz
1 0 1 0 0
Tone 7
Tone 5
7
Sweeping 2400/2900Hz at 1Hz
0 1 1 0 0
Tone 10
Tone 5
8
Siren 500/1200/500Hz at 0.3Hz
1 1 1 0 0
Tone 2
Tone 5
9
Sawtooth 1200/500Hz at 1Hz
0 0 0 1 0
Tone 15
Tone 2
10
Alternating 2400/2900Hz at 2Hz
1 0 0 1 0
Tone 7
Tone 5
11
Intermittent
1000Hz
at
0.5Hz
General alarm
0 1 0 1 0
Tone 31
Tone 1
12
Alternating 800/1000Hz at 0.875Hz
1 1 0 1 0
Tone 4
Tone 5
13
Intermittent 2400Hz at 1Hz
0 0 1 1 0
Tone 15
Tone 5
14
Intermittent 800Hz 0.25s on 1s off
1 0 1 1 0
Tone 4
Tone 5
15
Continuous at 800Hz
0 1 1 1 0
Tone 2
Tone 5
16
Intermittent
660Hz
150mS
on,
150mS off
1 1 1 1 0
Tone 18
Tone 5
17
Alternating 544Hz
(100mS)/440Hz(400mS)
0 0 0 0 1
Tone 2
Tone 27
18
Intermittent 660Hz 1.8s on, 1.8s off
1 0 0 0 1
Tone 2
Tone 5
19
1400Hz to 1600Hz sweep up over
1s - 1600Hz to 1400Hz sweep down
over 0.5s
0 1 0 0 1
Tone 2
Tone 5
20
Continuous 660Hz
1 1 0 0 1
Tone 2
Tone 5
21
Alternating 554/440Hz at 1Hz
0 0 1 0 1
Tone 2
Tone 5
22
Intermittent 554Hz at 0.875Hz
1 0 1 0 1
Tone 2
Tone 5
23
800Hz pulsing at 2Hz
0 1 1 0 1
Tone 6
Tone 5
24
Sweeping 800/1000Hz at 50Hz
1 1 1 0 1
Tone 29
Tone 5
25
Sweeping 2400/2900Hz at 50Hz
0 0 0 1 1
Tone 29
Tone 5
26
Simulated bell sound
1 0 0 1 1
Tone 2
Tone 1
27
Continuous 554Hz
0 1 0 1 1
Tone 26
Tone 5
28
Continuous 440Hz
1 1 0 1 1
Tone 2
Tone 5
29
Sweeping 800/1000Hz at 7Hz
0 0 1 1 1
Tone 7
Tone 5
30
420Hz repeating 0.625s on, 0.625s
off
Australian alert signal
1 0 1 1 1
Tone 32
Tone 5
31
1200/500Hz at 1 Hz
Prepare to Abandon Platform
0 1 1 1 1
Tone 11
Tone 1
32
Sweeping 500/1200Hz 3.75s on,
0.25s off 15Hz
1 1 1 1 1
Tone 26
Tone 1
Figure 7
BExS110D AC Sounder
DIP Switch
Volume Control
Stage Terminals
AC Terminals
S2
S3
C
N
L