ABLE BEXS110D Скачать руководство пользователя страница 6

14)

 Tone Selection and 2nd and 3rd Stage Alarms

The BExS120D and BExS110D sounders have 32 different
tones that can be selected for the first stage alarm. The
sounders can then be switched to sound second and third
stage alarm tones. The tones are selected by operation of a
DIP switch on the pcb for both DC and AC units. The tone
table on page four shows the switch positions for the 32
tones and which tones are available for the second and third
stages. To operate the sounder on stage one simply connect
the supply voltage to the normal supply terminals (+ve and –
ve for DC units, L and N for AC units).

The operation of the second and third stages is different for
DC and AC units.

DC Units Second and Third Stage Tone Selection

The BExS120D and BEx110D DC sounders have the facility
to use ve or –ve switching to change the tone to the
second and third stages. For –ve switching connect the two
headers on the pcb to the left-hand (marked –ve) and centre
pins. For +ve switching connect the headers to the right hand
(ve) and the centre pins. To change to the second
stage tone, connect either a -ve or +ve supply line to terminal
S2, depending on which switching mode is being used while
maintaining the dc supply to the +ve and –ve terminals.
Similarly for the third stage tone, connect a -ve or +ve supply
line to terminal S3. The supply to the S3 terminal will
automatically override a supply to the S2 terminal.

AC Units Second and Third Stage Tone Selection

To select the second and third stage tones on the BExS120D
and BExS110D AC sounders the Common (C) terminal on
the three way terminal block on the pcb is connected to the
S2 terminal for the second stage tone and the S3 terminal for
the third stage tone.

15)

Volume Control

All BExS120D and BExS110D sounders, with the exception
of 12V DC units, have a volume control to adjust the output
level.

To

set

the

required

output

level,

adjust

the

potentiometer on the pcb. For maximum output level the
potentiometer should be set to the fully clockwise position.

16)

End of Line Monitoring (DC Units)

On BExS120D and BExS110D DC units, dc reverse line
monitoring can be used if required. All DC sounders have a
blocking diode fitted in their supply input lines. An end of line
monitoring diode or an end of line monitoring resistor can be
connected across the +ve and –ve terminals. If an end of line
resistor is used it must have a minimum resistance value of
3k3 ohms and a minimum wattage of 0.5 watts or a minimum
resistance value of 500 ohms and a min. wattage of 2 watts.

TONE SELECTION TABLE

Tone Selection

DIP Switch
Settings

Stage Selection

Stage 1

Frequency Description

1 2 3 4 5

Stage 2

Stage 3

1

Continuous 1000Hz

Toxic Gas Alarm

0 0 0 0 0

Tone 31

Tone 11

2

Alternating 800/1000Hz at 0.25s
intervals

1 0 0 0 0

Tone 17

Tone 5

3

Slow Whoop 500/1200Hz at 0.3Hz
with 0.5s gap repeated

0 1 0 0 0

Tone 2

Tone 5

4

Sweeping 800/1000 at 1Hz

1 1 0 0 0

Tone 6

Tone 5

5

Continuous at 2400Hz

0 0 1 0 0

Tone 3

Tone 27

6

Sweeping 2400/2900Hz at 7Hz

1 0 1 0 0

Tone 7

Tone 5

7

Sweeping 2400/2900Hz at 1Hz

0 1 1 0 0

Tone 10

Tone 5

8

Siren 500/1200/500Hz at 0.3Hz

1 1 1 0 0

Tone 2

Tone 5

9

Sawtooth 1200/500Hz at 1Hz

0 0 0 1 0

Tone 15

Tone 2

10

Alternating 2400/2900Hz at 2Hz

1 0 0 1 0

Tone 7

Tone 5

11

Intermittent

1000Hz

at

0.5Hz

General alarm

0 1 0 1 0

Tone 31

Tone 1

12

Alternating 800/1000Hz at 0.875Hz

1 1 0 1 0

Tone 4

Tone 5

13

Intermittent 2400Hz at 1Hz

0 0 1 1 0

Tone 15

Tone 5

14

Intermittent 800Hz 0.25s on 1s off

1 0 1 1 0

Tone 4

Tone 5

15

Continuous at 800Hz

0 1 1 1 0

Tone 2

Tone 5

16

Intermittent

660Hz

150mS

on,

150mS off

1 1 1 1 0

Tone 18

Tone 5

17

Alternating 544Hz
(100mS)/440Hz(400mS)

0 0 0 0 1

Tone 2

Tone 27

18

Intermittent 660Hz 1.8s on, 1.8s off

1 0 0 0 1

Tone 2

Tone 5

19

1400Hz to 1600Hz sweep up over
1s - 1600Hz to 1400Hz sweep down
over 0.5s

0 1 0 0 1

Tone 2

Tone 5

20

Continuous 660Hz

1 1 0 0 1

Tone 2

Tone 5

21

Alternating 554/440Hz at 1Hz

0 0 1 0 1

Tone 2

Tone 5

22

Intermittent 554Hz at 0.875Hz

1 0 1 0 1

Tone 2

Tone 5

23

800Hz pulsing at 2Hz

0 1 1 0 1

Tone 6

Tone 5

24

Sweeping 800/1000Hz at 50Hz

1 1 1 0 1

Tone 29

Tone 5

25

Sweeping 2400/2900Hz at 50Hz

0 0 0 1 1

Tone 29

Tone 5

26

Simulated bell sound

1 0 0 1 1

Tone 2

Tone 1

27

Continuous 554Hz

0 1 0 1 1

Tone 26

Tone 5

28

Continuous 440Hz

1 1 0 1 1

Tone 2

Tone 5

29

Sweeping 800/1000Hz at 7Hz

0 0 1 1 1

Tone 7

Tone 5

30

420Hz repeating 0.625s on, 0.625s
off

Australian alert signal

1 0 1 1 1

Tone 32

Tone 5

31

1200/500Hz at 1 Hz

Prepare to Abandon Platform

0 1 1 1 1

Tone 11

Tone 1

32

Sweeping 500/1200Hz 3.75s on,
0.25s off 15Hz

1 1 1 1 1

Tone 26

Tone 1

Figure 7

BExS110D AC Sounder

DIP Switch

Volume Control

Stage Terminals

AC Terminals

S2
S3

C

N

 L

Содержание BEXS110D

Страница 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BEXS110D BEXS120D ...

Страница 2: ...ley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0 1224 725999 Email ab able co uk Internet www able co uk e procurement www 247able com Registered in England No 01851002 VAT No GB 417 2481 61 ...

Страница 3: ...of Enclosure d 4 Installation Requirements The sounders must be installed in accordance with the latest issues of the relevant parts of the BS EN 60079 specifications or the equivalent IEC specifications Selection Installation and maintenance of electrical apparatus for use in potentially explosive atmospheres other than mining applications or explosive processing and manufacture BS EN 60079 14 19...

Страница 4: ...hat a suitable power supply is used to run the sounders The power supply selected must have the necessary capacity to provide the input current to all of the sounders connected to the system The following table shows the input current taken by the various sounder units Unit Type Input Input Max Voltage Current I P Volts BExS120D 24V DC 800mA 30V BExS120D 12V DC 850mA 15V BExS120D 48V DC 420mA 58V ...

Страница 5: ... one cable entry is used the other one must be closed with an Ex d flameproof blanking plug which must be suitably approved for the installation requirements 13 Cable Connections The cable connections are made into the terminal blocks on the electronic pcb assembly located in the flameproof enclosure See section 8 of this manual for access to the flameproof enclosure On the AC units a two way term...

Страница 6: ... or an end of line monitoring resistor can be connected across the ve and ve terminals If an end of line resistor is used it must have a minimum resistance value of 3k3 ohms and a minimum wattage of 0 5 watts or a minimum resistance value of 500 ohms and a min wattage of 2 watts TONE SELECTION TABLE Tone Selection DIP Switch Settings Stage Selection Stage 1 Frequency Description 1 2 3 4 5 Stage 2 ...