8.3.3  Alarm enable:  ‘EnbL’

This function allows each alarm to be enabled or
disabled without altering any of the alarm
parameters. To enable or disable the alarm select
'EnbL' from the alarm menu and press 

P

 which will

reveal the current setting ‘on’ or ‘oFF’.  The
function can be changed by pressing the 

 or 

button followed by the 

E

 button to return to the

alarm menu.

8.3.4  Setpoint adjustment:   ‘SP1’ and ‘SP2’

The setpoint of each alarm may be positioned
anywhere in the numerical display of the indicator
providing that this corresponds to an input current
between 3.8 and 20.2mA. e.g. If the indicator has
been calibrated to display 0 with 4mA input and
10000 with 20mA input, the two alarm setpoints
may be positioned anywhere between  -125 and
10125.
To adjust the setpoint select 'SP1' or 'SP2' from the
alarm configuration menu and press 

P

 

which will

reveal the existing alarm setpoint.  The flashing
digit of the setpoint can be adjusted using the 

and 

 push-buttons, and the 

P

 button to move

control to the next digit.  When the required
setpoint has been entered press 

E

 

to return to the

alarm configuration menu.
The alarm setpoints may also be adjusted when
the indicator is in the display mode, see section
8.3.12.

8.3.5  Alarm function:   ‘Hi.Lo’

Each alarm can be independently conditioned as a
high alarm or as a low alarm.   To check or change
the alarm function select 'Hi.Lo' from the alarm
menu and press 

P

 to reveal the current setting.

The function can be changed by pressing the 

 or

 button followed by the 

E

 button to return to the

alarm menu.

8.3.6  Alarm output status:   ‘no.nC’

Configures the solid state alarm output to be open
‘no’ or to be closed ‘nC’ in the non-alarm condition.
When deciding which is required, care should be
taken to ensure that the alarm output is fail safe as
illustrated in Fig 9.

‘no’ Alarm output open in non-alarm condition

‘nC’ Alarm output closed in non-alarm condition

CAUTION

When the 4/20mA supply is removed from the
loop powered indicator, both alarm outputs
will open irrespective of conditioning.
Therefore for fail safe operation both alarm
outputs should be conditioned to be open in
the alarm condition ‘nC’.

To check or change the alarm output status, select
'no.nC' from the alarm configuration menu and
press 

P

 to reveal the setting.  The function may be

changed by pressing the 

 or 

 button followed

by the 

E

 

button to return to the alarm configuration

menu.

8.3.7  Hysteresis:   HStr

Hysteresis is shown in the units that the indicator
has been calibrated to display.
To adjust the hysteresis select 'HStr' from the
alarm menu and press 

P

 which will reveal the

existing figure.  The flashing  digit can be adjusted
using the 

 and 

 push-buttons, and the 

P

button will move control to the next digit.  When the
required hystersis has been entered press 

E

 

to

return to the alarm configuration menu.

e.g.  An indicator calibrated to display 0 to 10000,
with a high alarm set at 9000 and hysteresis of 200
will perform as follows:

The high alarm will be activated when
increasing indicator display equals 9000, but
will not reset until the indicator display falls
below 8800.

8.3.8  Alarm delay:   dELA

This function delays activation of the alarm output
for an adjustable time following the alarm condition
occurring.  The delay can be set in 1 second
increments between 0 and 3600 seconds.  If a
delay is not required zero should be entered.  To
adjust the delay select 'dELA' from the alarm
configuration menu and press 

P

 which will reveal

the existing delay.  The flashing digit of the delay
can be adjusted using the 

 and 

 push-buttons,

and the 

P

 button to move control to the other

digits.  When the required delay has been entered
press 

E

 

to return to the alarm menu.

e.g.  An indicator with a high alarm set at 9000 and
an alarm delay of 30 seconds will perform as
follows:

The alarm annunciator will start to flash when an
increasing indicator display equals 9000, but the
alarm output will not be activated until the alarm
condition has existed continuously for 30 seconds.
When the alarm output is activated, the alarm
annunciator will stop flashing and become
permanently activated.

If the ‘FLSH’ function, which flashes the indicator
display when an alarm occurs, has been enabled,
it will not start to function until the alarm output is
activated.
See section 8.3.11

Содержание BEKA BA504E

Страница 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA504E BA524E...

Страница 2: ...hill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0 122...

Страница 3: ...Issue 4 14th March 2014 BA504E BA524E General Purpose loop powered field mounting indicators Issue 4...

Страница 4: ...ver range 6 5 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Custom...

Страница 5: ...e g temperature flow pressure or level The BA504E and BA524E are not certified for use in explosive atmospheres For hazardous area application the BA304E BA304NE BA324E or the BA324NE should be used 2...

Страница 6: ...indicator and the ACSP access setpoints in display mode function has been enabled P E Provides access to the configuration menu via optional security code Note BA524E only If the indicator has been c...

Страница 7: ...or linking cable screens The indicator s earth terminal is connected to the carbon loaded GRP enclosure If this enclosure is not bolted to an earthed post or structure the earth terminal should be con...

Страница 8: ...EMC Both instruments compy with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs with the screens connected at one poin...

Страница 9: ...tion Default Configuration BA504E BA524E Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph...

Страница 10: ...8...

Страница 11: ...n 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or pre...

Страница 12: ...etween the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the...

Страница 13: ...n and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit secur...

Страница 14: ...r volumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break point required should f...

Страница 15: ...13...

Страница 16: ...dd a break point Adds a new break point before the displayed break point The calibration of existing break points is not changed but the identification number of all subsequent break point is increase...

Страница 17: ...tor display at the first break point When set as required press E to return to the 0 n prompt from which the the next break point can be selected using the or buttons When the required break point has...

Страница 18: ...If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop w...

Страница 19: ...n Both indicators can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9...

Страница 20: ...polarised and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 10 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switc...

Страница 21: ...19...

Страница 22: ...setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function as High or Low See section 8 3 5 no nC Normally open or...

Страница 23: ...r fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Страница 24: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Страница 25: ...int plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 14 Fig 14 Displayed value and setpoints on bargra...

Страница 26: ...cting it in series with the indicator s 4 20mA input as shown in Fig 16 which increases the maximum indicator voltage drop from 1 2 to 5V Fig 16 Loop powered backlight Providing the increased voltage...

Страница 27: ...l pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel b...

Отзывы: