Auto configure is the first step to take after the panel is initially energized. This function recognizes
the electrical system, then automatically sets all the system parameters: system voltage, frequency,
and phase sequence. Follow the steps in the figure on the HMI to run auto configure. The ATS must
have at least one source available to complete this step.
S1 Connected to Load
Load Current
393 A
11:06
60s
G
Override S1 Fail
TruONE ATS
System Overview
S1
Ok Not Ok
S2
Operation
Parameters
Measurements
About
Test
Settings
TruONE ATS
—
Auto Configure
Figure 5