IU Protection
I6
t
t6
I
IU
Function
The protection trips if the current readings are unbalanced; the protection sends a TRIP command if the
detected unbalance exceeds threshold I6 for longer than t6.
The protection is automatically self-excluding in two cases:
• the measurement of at least one current exceeds 6 In
• the maximum current among all the phases is less than 0.3 In
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 87)
• the graph with trip curve (page 99)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters menu OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled, the
alarm and exceedance of protection time are only managed as information
OFF
Version
Allows the unbalance calculation mode to be selected:
• Old: % Sbil = 100 x (I
max
- I
min
) / I
max
• New: % Sbil = 100 x (Δmax I
mi
) / I
mi
NOTE
:Δmax I
mi
: maximum deviation among the measured currents,
calculated by comparing each current with the mean value;
I
mi
: mean value of the current readings
Old
Threshold I6
Establishes the unbalance value that trips the protection.
Unbalance is given in percentage value within the range: 2% to 90% with 1%
steps.
50 %
Time t6
This is the trip time of the protection; the value is given in seconds and can be
set within a range: 0.5 s to 60 s, in 0.5 s steps
5 s
Ekip M Touch
With Ekip M Touch, IU protection features the following differences compared to the other models:
• version set as New, non-editable
• protection is inhibited if the rms value of at least one of the phase currents is less than 0.25 In.
Neutral Protection
Function
Neutral protection characterizes protections L, S and I differently on the neutral phase by introducing a
different control factor from the other phases.
The protection is available with the 4P and 3P + N configuration; the configuration parameters can be
accessed via the Settings menu (page 37).
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection
OFF
Neutral
threshold
Defines the multiplicative factor applied to the trip thresholds and curves of
the protections for the current read on phase Ne:
• 50 %: lowest trip thresholds for the neutral current
• 100 %: same trip thresholds for all phases
• 150 %: highest trip thresholds for the neutral current
• 200 %: highest trip thresholds for the neutral current
50 %
Limitations and additional functions
Ekip Touch rejects modification of thresholds I1 and InN in the absence of the following limitation: (I1 x InN)
≤
Iu
• I1 is the threshold of L protection in Amperes (example: In= 800 A and I1= 0.6 becomes I1= 480 A)
• InN is the neutral threshold expressed as multiplicative factor (example: InN= 200% becomes InN= 2)
• Iu is the size of the CB
WARNING! With 150% and 200% threshold; if the measured neutral current exceeds
16In, the Trip unit resets the protection to 100% by itself
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...