background image

MOUNTING INSTRUCTIONS

3 of 4

2 of 4

WIRING INSTRUCTIONS

Dispart mounting plate

Mounting plate

   Insert 

fl

at screwdriver into slot on side of unit, pry off and remove 

   the mounting plate from unit.
   Disconnect AC connector from PCBA.

a

b

Wall mounting or Ceiling mounting

    Knock out appropriate center cable entry hole and mounting screw 
    hole on the mounting plate.
    Route AC supply wire through center hole of mounting plate.
    Fix mounting plate on the mount surface with screws and anchor nuts. 

a

b

c

 Connect the AC supply wire to terminal block. Refer to wiring 
 instruction showed below.

Connect battery male and female connector inside of mounting
bracket.

Remove the pictogram on the unit, select other pictogram you need

then insert into slot of panel.

Snap AC supply on PCBA and then snap fixture to mounting 

plate.

Suitable cable 0.75-2.5mm²

Wiring connection

Connect battery

Change pictogram when necessary

Finish installation

 Non-Maintained Wiring

 Maintained Wiring

Maintained (default operation):
Connect L,N and leave jumper cable connected.

Non-maintained:
Connect L,N and remove jumper cable.

MOUNTING OPTIONS

Wall  mounting

Ceiling mounting

PICTOGRAM STYLES

PRECAUTIONS

Carefully read this instruction leafet before installing or using the luminaire. 
This leafet provides important information about the correct installation, use, maintenance and disposal 
of this product. Please observe the following guidelines:
1. Installation must be in accordance with European installation requirements HD 60364 and additional local 
 regulations.
2. This product may not be modified in any way what so ever or used for a purpose or in an environment 
other than for which it is designed. Failing to observe these guidelines will invalidate the warranty and the 
CE-compliance of this product.
3. The luminaire is suitable for indoor use only
4. Before installing the luminaire, the supply must be isolated.
5.The luminaire should be connected to the voltage equivalent to that indicated on the type label

SERVICE & OPERATION

Normal Operation: 

The green indicator light on face plate stays on. The LED will go out if the mains supply 

fails, the internal charger malfunctions, or the unit is in test mode.

Battery:

 Sealed Ni-Cad or Ni-Mh rechargeable battery pack. Battery should be replaced when the required 

duration is no longer achieved. To avoid any damage to the fixture and ensure its performance, the battery 
should be replaced with same brand and type.

Test Switch:

 Press the test switch button, LED indicator will go out and the sign will be illuminate from its

battery pack.

WARNING:

The luminaire must, under no circumstances, be covered with insulating material or similar material only 

Commissioning Test Behaviour

Initial connection of the mains supply will initiate a commissioning sequence where the battery will 
remain on charge and test for an uninterrupted 60 hours. Any interruption of the mains supply during
this period will reset the counter to zero.
The sequence is : to charge for 24hours. Having fully charged the battery, then execute a duration test.
Upon successful completion of the duration test, the gear will perform another full charge period of 
24hours. After this period, it is suggested to perform a function test and then check for successful 
completion of the function and duration tests.
Therefore, after initial mains power on, it is best to leave the gear alone for 60 hours to allow the gear
to complete its pre-programmed commissioning testing. During the 60 hour period, any attempt
to have the gear perform a function or duration test will simply result in the requested test being 
'pended'. Following the commissioning test it will then perform whatever tests are pended. Meaning 
that if you had pressed "start duration test", at the end of commissioning, the gear will perform 
another duration test and another subsequent charge period before normal operations could be 
resumed.

Gear Behaviour After Battery Change (meaning Disconnect / Reconnect battery)

After changing the battery, the gear will perform a complete commissioning sequence, as described
above,irrespective of the condition of the battery.

Function test

A 5 second functional test is carried out at nominally 1 week interval.

Duration test

The gear switches to battery supply with mains supply off, and runs until the batteries can no longer 
supply the lamp
The length of time to run out is recorded in memory.
A pass result indicates the battery powered the fitting and lamp for the rated period of this fitting.
A full rated duration test is carried out nominally at 52 weeks intervals.

In DALI mode, the start of the regular duration and function tests, is initiated by the attached controller.
If the DALI controller is not available, the gear will revert to its automated settings.

Ceiling mounting

Wall mounting 

DALI Connection

Battery Connection

AC connector

Отзывы: