WaterMaster FET100
Electromagnetic floweter
|
Transmitter
4 Start-up and Operation
26
OI/FET100–EN Rev. A
* For OIML and MID flowmeters, only m
3
must be used.
Parameter
Range
[Default]
Note
Language
English, Deutsch, Français, Español,
Italiano, Polski, Portuguese
[English] Selectable
Q (Flowrate) Unit
m
3
/s, m
3
/min, m
3
/h, m
3
/d, ft
3
/s, ft
3
/min,
ft
3
/h, ft
3
/d, ugal/s, ugal/min, ugal/h,
ugal/d, Mugal/d, igal/s, igal/min, igal/h,
igal/d, bls/s, bls/min, bls/h, bls/d, hl/h,
ml/s, ml/min, l/s, l/min, l/h, Ml/d,
[m
3
/h] Selectable
Qmax
Dependent on sensor size
[Factory set]
Volume & Pulse Unit
m
3
, l, ml, ft
3
, hl, igal, ugal, bls, MI, Mugal
Selectable*
Pulse Width
0.09 to 2000.00 ms
[0.09 ms] Editable
Pulses / Unit
0.000010 to 10,000,000 pulses / unit
[1.0] Editable
(Only shown when Pulse
Mode is Pulse / Unit)
Fullscale Frequency
0.250000 to 10,000,000 Hz
[5,000.000] Editable
(Only shown when Pulse
Mode is Fullscale Frequency)
Damping
0.02 to 60 s
[3.00 s] Editable
Mains Frequency
50 or 60 Hz
[50 Hz] Selectable