10.3.3 Wiring diagrams for C.B. on withdrawable part
-MS
Supply voltage
-RL2
Blocking magnet for withdrawable part
with rectifier –TR5
-RL1
Closing lock-out (closed circuit)
-MO1
Switching command OFF 1 (open circuit)
-MC
Switching command ON (open circuit)
-MU
Undervoltage release (closed circuit)
-MO2
Switching command OFF 2 (open circuit)
-BB1
Auxiliary switch on the actuating shaft
-BB3
Auxiliary switch on the actuating shaft
-BB4
Fleeting contact (100 ms)
-BT2
Limit switch for withdrawable part in
test position
-BT1
Limit switch for withdrawable part in
service position
-DR
READY for operation (NOC)
-DN
NOT READY for operation (NCC)
-DO1
OFF signal (NOC)
-DC1
ON signal (NOC)
-DO2
OFF-Signal (NOC) (Full version)
-DC2
ON-Signal (NOC) (Full version)
See page 50 for comparison of IEC/VDE
designations.
Mode of presentation:
(
1
) Connection exists when auxiliary switches -BB1
and -BB3 are not used
(
2
) Full version
Note:
If the READY contact -DR is to be polled, the
wiring diagram of the panel should include the
information that this contact is already connected
to blocking magnet -RL2 and is therefore not
isolated.
Figure 10/10: Wiring diagramm for VM1 vacuum circuit
breaker on manually movable
withdrawable assembly.
- Maximum of equipment
- Control wiring plug 58-pole
- Use in panel system ZS1, UniGear-Type
ZS1, UniSafe, Power-bloc and Mounting
frame
48 VM1 Vacuum circuit-breaker
| Instruction manual 504/05
-MS
Supply voltage
-RL2
Blocking magnet for withdrawable part with rectifier –TR5
-RL1
Closing lock-out (closed circuit)
-MO1
Switching command OFF 1 (open circuit)
-MC
Switching command ON (open circuit)
-MU
Undervoltage release (closed circuit)
-MO2
Switching command OFF 2 (open circuit)
-BB1
Auxiliary switch on the actuating shaft
-BB3
Auxiliary switch on the actuating shaft
-BB4
Fleeting contact (100 ms)
-BT2
Limit switch for withdrawable part in test position
-BT1
Limit switch for withdrawable part in service position
-DR
READY for operation (NOC)
-DN
NOT READY for operation (NCC)
-DO1
OFF signal (NOC)
-DC1
ON signal (NOC)
-DO2
OFF-Signal (NOC) (Full version)
-DC2
ON-Signal (NOC) (Full version)
See page 52 for comparison of IEC/VDE designations.
Mode of presentation:
1)
Connection exists when auxiliary switches -BB1 and -BB3 are not used
2)
Full version
Note:
If the READY contact -DR is to be polled, the wiring dia-
gram of the panel should include the information that this
contact is already connected to blocking magnet -RL2 and
is therefore not isolated.
Note:
The wiring diagrams comprise the basic com ponents and all fur-
ther equipment options for the various VM1 types. The scope of
10.3.3 Wiring diagrams for C.B. on withdrawable part
equipment possible within an individual type series is listed in the
relevant switchgear list, and the euquipment fitted in each individ-
ual case can be found in the order documentation.
Figure 10/10: Wiring diagramm for VM1 vacuum circuit-breaker on
manually movable withdrawable assembly.
- Maximum of equipment
- Control wiring plug 58-pole
- Use in panel system ZS1, UniGear-Type ZS1, UniSafe,
Power-bloc and Mounting frame
BA 504-05 GB_29102012.indd 48
30.10.12 13:45
Note:
The wiring diagrams comprise the basic components and
all further equipment options for the various VM1 types.
The scope of equipment possible within an individual
type series is listed in the relevant switchgear list, and
the euquipment fitted in each individual case can be
found in the order documentation.
—
10. Technical data
Содержание VM1
Страница 51: ...MEDIUM VOLTAGE PRODUCTS 51 51...