![ABB VAC D500 Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/abb/vac-d500/vac-d500_commissioning-instructions_5481019.webp)
D500
| CI/EDP300-EN Rev. A 19
6
Commissioning
hange from one to two columns
During commissioning, the mechanical mounting on the linear
and part-turn actuators is checked. For this purpose, the
actuator is first moved into the end positions and Auto Adjust
is then carried out.
6.1
Checks prior to commissioning
Air pressure in the compressed air connecting line:
1.4 … 10 bar (20 … 145 psi)
Current input active:
4 … 20 mA
6.2
Mechanical mounting checks
6.2.1
Moving to end positions following completion of
Auto Adjust
Process display
1.
Use
to switch to the Operating Mode menu.
Operating Mode
Auto
Adjust
O
Adaptive
O
Control
O
Manual SP
O
Manual Sensor
Configuration
Back
OK
2.
Use
or
to select the "Manual Sensor" operating
mode.
3.
Use
and
to move to the relevant end positions.
-45.0
Pos. Ang.
°
Check the end positions. The angle of rotation is displayed in
degrees.
Recommended range:
— between -30 … 30° for linear actuators
— between -45 … 45° for part-turn actuators
6.2.2
Moving to end positions with a new device
Process display
Electronic
1.
Use
and
to move to the relevant end positions.
-45.0
Pos. Ang.
°
Check the end positions. The angle of rotation is displayed in
degrees.
Recommended range:
— between -30 … 30° for linear actuators
— between -45 … 45° for part-turn actuators
Auto Adjust must then be performed. The "Starting Auto
Adjust" section describes how Auto Adjust is performed.