Mounting the adapter on the positioner
Fig. 13
1.
Determine the mounting position (parallel to actuator or at
90° angle).
2.
Determine the direction of rotation of the actuator
(clockwise or counter-clockwise).
3.
Move the part-turn actuator into the home position.
4.
Pre-adjust feedback shaft.
To ensure the positioner will operate within the working
range (see Fig. 2), the mounting position as well as the
home position and direction of rotation of the actuator
must be taken into account when determining the adapter
position on the feedback shaft (1). For this purpose, the
feedback shaft can be adjusted manually so that the
adapter (3) can be attached in the correct position.
5.
Attach the adapter to the feedback shaft in the correct
position and fasten with threaded pins (2). One of the
threaded pins must be locked in place on the flat side of
the feedback shaft.
Screwing the mounting bracket onto the positioner
Fig. 14
1 Mounting bracket
Screwing positioner onto actuator
Fig. 15
IMPORTANT (NOTE)
After mounting, check whether the working range
for the actuator matches the sensor range for the
positioner.