Contactor
VSC7-VSC/P
7
VSC12-VSC/P 12
Rated voltage
[kV]
2.2/2.5
3.6
3.6/7.2
6.2/7.2
12
Ultimate performances for:
Motors
[kW]
1.000
1.500
1.500
3.000
5.000
Transformers
[kVA]
1.100
1.600
2.000
4.000
5.000
Capacitors
[kVAR]
1.000
1.500
1.500
3.000
4.800 (1)
Ultimate performances for back-to-back
capacitor
banks
Rated current
[A]
250
250
250
250
Contact ABB
Max. transient current of the capacitor
[kA]
8
8
8
8
Contact ABB
Max. transient frequency of the capacitor
[kHz]
2.5
2.5
2.5
2.5
Contact ABB
(1) Overvoltage surge ar-
resters are compulsory
between phases and
between phase and
earth.
Un
24 ... 250 V AC-DC
Rated current
Ith
2
= 10 A
Insulation voltage
2500 V 50 Hz (per 1 min)
Electric resistance
3 mOhm
Rated current and breaking capacity in category AC11 and DC11
Un
Cos
ϕ
T
In
Icu
220 V ~
0,7
—
2,5 A
25 A
24 V –
—
15 ms
10 A
12 A
60 V –
—
15 ms
6 A
8 A
110 V –
—
15 ms
4 A
5 A
220 V –
—
15 ms
1 A
2 A
1.5. Contactor auxiliary circuits
10 auxiliary contacts (5 normally open and 5 normally closed) are available on the contactor for
the customer’s use, with the following characteristics.
1.6. Compliance with Standards
V-Contact contactors comply with the Stan-
dards of the major industrialised countries and
in particular with the following Standards:
– IEC 60470 (2000) and IEC 632-1 (1978) for
the contactor;
– IEC 60694 (2002).
1.7. Protection against short-circuit
The value of the installation short-circuit cur-
rent could exceed the breaking capacity of the
contactor. The contactor must therefore have
adequate protection against short-circuit.
Fuse replacement must only be car-
ried out by qualified personnel.
1.4. Performances
!