ABB
5
Uniswitc h Operation a nd
Mainte na nc e Manua l
UNI S14GB 05-02
2 Technical
data
2.1 Electrical data
Table 2.1
Electrical data
Rated voltage U
r
kV
12
17.5
24
Rated lightning impulse withstand voltage U
p
kV
Common value
75
95
125
Across the isolating distance
85
110
145
Rated power-frequency withstand voltage U
d
kV
Common value
28
1
38
1
50
Across the isolating distance
32
1
45
1
60
Rated frequency
Hz
50/60
50/60
50/60
Rated current I
r
A
Busbar
630/1250
630/1250
630/1250
Feeder
630/1250
630/1250
630/1250
Rated short-time withstand current
2
kA
Main circuit
25
20
20
Earthing circuit
25
20
20
Rated duration of short circuit
s
2
3
3
Rated peak withstand current
kA
62,5
50
50
Degree of protection (IP-code)
For the enclosure
IP 2XC
IP 2XC
IP 2XC
For the partitions
IP 2X
IP 2X
IP 2X
Mechanical endurance of switch-disconnector
Times
Closed/Open
1000
1000
1000
Open/Earthed
1000
1000
1000
SF6-gas in switch-disconnector
Bar
Rated filling pressure
1,4
1,4
1,4
Minimum operating pressure
1,3
1,3
1,3
1
Higher values are possible if required by other national standards.
2
The short-circuit withstand capacity of the instrument transformers must be taken into account
separately.