References
Further details about installation and equipping the switchgear can be
obtained from the order documents.
3.2.3 Service
continuity
LSC Category
For switchgear the Loss of Service Continuity Category (LSC) describes
the extent to which other compartments and/or functional units may
remain energised when a main circuit compartment is opened.
According to IEC 62271-200 the Loss of Service Continuity (LSC) of
Uniswitch switchgear is LSC2A-PI. The PI denotes that partition and
shutters are insulation.
Table 3.1
Accessibility to compartments (according to IEC 62271-200).
Part of the switchgear that can be left energised
Cable corresponding to the
functional unit
All other functional units
Fuse/cable No
Yes
Busbar
Not relevant: non-accessible
Not relevant: non-accessible
Circuit-breaker (fixed)
No
Yes
Circuit-breaker
(withdrawable)
No Yes
Compartment to
be opened
Low voltage
Yes
Yes