Cable to bus ZVC-CTB Ratings
Circuit full load current
Rated frequency
Rated voltage
Width
Depth
1
Height
2
A
Hz
kV
mm
mm
mm
400
50/60
7.2
325
1304
2200
1 Bottom power cable entry version. Top cable power entry version
1554 mm with gas duct.
2 Larger LV compartment with corresponding total panel height
2400 and 2596 mm available.
Refer to shipping sections in the general
arrangement drawing.
Note the location of the power cable entry in the
contract drawings.
Pay special attention to clauses 6.4 to join
panels and 6.5 to install busbars.
Transformer feeder ZVC
Ratings
Circuit full load
current
Rated frequency
Rated voltage
Width
Depth1
Height2
A
Hz
kV
mm
mm
mm
400
50/60
7.2
325
1304
2200
1 Bottom power cable entry version. Top cable power entry version
1554 mm with gas duct.
2 Larger LV compartment with corresponding total panel height
2400 and 2596 mm available.
Refer to shipping sections in the general
arrangement drawing.
Note the location of the power cable entry in the
contract drawings.
Pay special attention to clauses 6.4 to join
panels and 6.5 to install busbars.
Double feeder ZVC-DF Ratings
Circuit full load current
Rated frequency
Rated voltage
Rated frequency
withstand
Rated tmpuse withstand
Short time current-3 sec
Width
Depth
1
Height
2
A
Hz
kV
kV
kVpx
kA
mm
mm
mm
400
50/60
7.2
32
50
50
325
1304
2200
1 Bottom power cable entry version. Top cable power entry version
1554 mm with gas duct.
2 Larger LV compartment with corresponding total panel height
2400 and 2596 mm available.
Refer to shipping sections in the general
arrangement drawing.
Note the location of the power cable entry in the
contract drawings.
Pay special attention to clauses 6.4 to join
panels and 6.5 to install busbars.
4.7.3 Transformer feeder
4.7.4 Conveyor belt double motor feeder
4.7.5 Cable to bus