If the optionally installed filter regulator is installed, it has to be checked regularly as well.
Additionally, the control position should be checked periodically for conformity with the
tolerance limit.
3.5.1 Functional test of the shutdown module
Proceed as described below:
1. Remove the cover.
2. Alternately set the slide switch (1) from the "On" position in the middle to the
top and bottom position ("Off1" or "Off2") and check that the actuator is depres-
surized properly.
3. Set the slide switch to the "On" position in the middle again.
4. Replace the cover.
!
WARNING
If the optional shutdown module is used, it must be subject to a functional
test every two years at the latest to ensure full operational reliability in
compliance with DIN V 19250. Otherwise, the AK4 approval will lapse.
Fig. 20
Slide switch (service switch) of the shutdown module
+41 -42
Limit 2
Limit 1
+85-86
+51 -52
+11 -12
1
On
Off2
Off1
Содержание TZIDC-110
Страница 38: ...38 Electro pneumatic positioner TZIDC 110 41 18 77 EN 5 Certificates...
Страница 39: ...41 18 77 EN Electro pneumatic positioner TZIDC 110 39...
Страница 40: ...40 Electro pneumatic positioner TZIDC 110 41 18 77 EN...
Страница 41: ...41 18 77 EN Electro pneumatic positioner TZIDC 110 41...
Страница 42: ...42 Electro pneumatic positioner TZIDC 110 41 18 77 EN...
Страница 43: ...41 18 77 EN Electro pneumatic positioner TZIDC 110 43...
Страница 44: ...44 Electro pneumatic positioner TZIDC 110 41 18 77 EN...
Страница 52: ...52 Electro pneumatic positioner TZIDC 110 41 18 77 EN...
Страница 53: ...41 18 77 EN Electro pneumatic positioner TZIDC 110 53...
Страница 54: ...54 Electro pneumatic positioner TZIDC 110 41 18 77 EN...
Страница 55: ...41 18 77 EN Electro pneumatic positioner TZIDC 110 55...