TZIDC-110, TZIDC-120
DIGITAL POSITIONER | OI/TZIDC-110/TZIDC-120-EN REV. H
11
ATEX / UKEX – ‘Ex ec’ type of protection
Ex-marking
Ex marking
Marking
II 3 G Ex ec IIC T6, T4 ... T1 Gc
Type examination
certificate (ATEX)
TÜV 02 ATEX 1943 X
Certificate (UKEX)
EMA22UKEX0032X
Type
Type of protection ‘ec’
Device class
II 3 G
Standards
EN 60079-7, EN 60079-0
Temperature data
Temperature class
Ambient temperature Ta
T4 to T1
−
40 to 85 °C
T6
−
40 to 50 °C
Electric Data
Current circuit (terminal) Electrical information (maximum values)
Signal circuit
(+11 / −12)
U = 9 to 32 V DC
I = 10.5 mA
Feedback on the actuator
position using proximity
switches,
(Pepperl & Fuchs SJ2-SN)
(Limit1: +51 / −52),
(Limit2: +41 / −42)
For maximum values, see EU-Type examination
certificate PTB 00 ATEX 2049 X Pepperl & Fuchs
Type 2 proximity switches
Local communication
interface (LCI)
Only for connection to a programming device
using an ABB LCI adapter (Um ≤ 30 V DC) outside
the hazardous area.
Special conditions
In the case of TZIDC-110, TZIDC-120, the following shall apply for
safe use in the Ex ‘ec IIC’ type of protection:
• Only devices that are suited for operation in hazardous
areas of Zone 2 and the conditions prevailing at the place
of use may be connected to circuits in Zone 2
(manufacturer's declaration or certificate from the test
center).
• For the ‘Mechanical digital feedback with Pepperl & Fuchs
SJ2-SN proximity switches’ circuit, external measures
must be implemented outside of the device to prevent
the rated voltage from being up-scaled by more than
40 % in the event of transient disturbances.
• It is only permissible to connect, disconnect, and switch
live circuits during installation or maintenance, or for the
purpose of carrying out repairs.
Note
It is considered very unlikely that a potentially hazardous
atmosphere would be present in Zone 2 at the same time
that installation or maintenance or repair work was being
carried out.
• Only non-flammable gases must be used for pneumatic
power supply.
• Only cable entries may be used that suit the requirements
of EN 60079-7 or EN 60079-15.
Содержание TZIDC-110
Страница 31: ...TZIDC 110 TZIDC 120 DIGITAL POSITIONER OI TZIDC 110 TZIDC 120 EN REV H 31 Page 2 of 5 ...
Страница 33: ...TZIDC 110 TZIDC 120 DIGITAL POSITIONER OI TZIDC 110 TZIDC 120 EN REV H 33 Page 4 of 5 ...
Страница 66: ...66 TZIDC 110 TZIDC 120 DIGITAL POSITIONER OI TZIDC 110 TZIDC 120 EN REV H Notes ...
Страница 67: ...TZIDC 110 TZIDC 120 DIGITAL POSITIONER OI TZIDC 110 TZIDC 120 EN REV H 67 Notes ...