ABB TTH200 Скачать руководство пользователя страница 9

 

TTH200, TTR200, TTF200 

 TEMPERATURE TRANSMITTER  |  SM/TTX200/SIL-EN REV. E 

9

 

7

 

Periodic proof test and maintenance 

 

According IEC 61508-2 proof tests shall be undertaken to reveal dangerous faults which are undetected by automatic diagnostic 
tests.  
The End User is responsible for selecting the type and the intervals according the overall safety system demands. 
The inspections must be conducted in a manner that enables users to verify the proper function of the safety equipment in 
combination with all related components. 
 

Proof Test 

The below described proof test is a recommended variant which could be performed within the required periodical proof test interval 
derived from the safety instrument system engineering demands (e. g. 1oo1, 1oo2 or 2oo3 architecture) and related PFD

AVG

 

calculations. 
 

Step 

Test Action (consecutive steps) 

Bypass the safety DCS or take other appropriate action to avoid a false trip. 

Restart, Power Down and Power Up the Device. 

Deactivate the device write protection (refer to the relevant operating instructions).  

Send a HART command, e. g. via EDD / DTM / FDI simulation functionality to the transmitter to go to the high alarm current output 
and verify that the analog current reaches that value.  
(Test for voltage problems such as a low loop power supply voltage or increased wiring resistance. This also tests for other possible 
electrical part failures). 

Send a HART command, e. g., via EDD/DTM/FDI simulation functionality to the transmitter to go to the low alarm current output and 
verify that the analog current reaches that value.  
(Test for possible quiescent current related failures)  

Activate the device write protection. (Refer to the relevant operating instructions) and wait at least 20 seconds for the non-volatile 
storage. 

Restore the loop to full operation by Restart, Power Down and Power Up the Device. 

Check the current output in performing a multi-point calibration (e. g., 5-point calibration) measurement of the temperature 
transmitter covering the applicable temperature range. (Test for possible sensor and electronics failures)  

Apply an adequate input signal (e.g., short circuit, wire break) to reach the pre-defined alarm level and verify that the safe state is 
reached. 
(Test for electronics failures that the analog current output corresponds to the provided input signal). 

10 

Remove the bypass from the safety DCS.  

Table 1:  ‘Suggested steps for proof test’ 

 

The test is assumed to detect 95 % of possible dangerous faults on the related temperature transmitter and sensor assembly. 
 
An appropriate simulator (Pt100 simulator, reference voltage sources) can also be used to check the transmitter electronics 
without sensor. 

 

 

 

 

Содержание TTH200

Страница 1: ...ction TTH200 TTR200 TTF200 electronics for sensor head field and rail mounting for standard and high measurement This document must be considered in conjunction with related operating instructions Add...

Страница 2: ...afe Failure Fraction SFF 7 Average probability of dangerous failure on demand PFDAVG 7 6 Constraints 8 7 Periodic proof test and maintenance 9 Proof Test 9 8 Installation commissioning configuration 1...

Страница 3: ...2 as single transmitter installation Up to SIL 3 as redundant transmitter installation Mode of safety operation Low Demand Mode Hardware Fault Tolerance HFT 0 as single transmitter installation 1oo1 A...

Страница 4: ...of failure per unit of time usually declared as FIT DD detected dangerous failures DU detected dangerous failures SD detected safe failures SU intrinsic safe failures PFDavg Average probability of dan...

Страница 5: ...s High vibration environment The operation is above 67 maximum rating according to specification NAMUR NE43 Standardization of the signal level for the breakdown information of digital 4 to 20 mA tran...

Страница 6: ...range from 20 0 to 23 6 mA The factory setting is 22 mA The low alarm current can be configured in a range from 3 5 to 4 0 mA The factory setting is 3 6 mA In the following cases and by some electric...

Страница 7: ...Germany with results reported within FMEDA Report 12 04 016 TTx200 R023 Version V3 Revision R0 The summarized results are attached within Appendix Exida FMEDA Report Note The systematic safety integr...

Страница 8: ...even when the current output is active with the configured high alarm The head mounted electronics TTH200 with IP00 rating according IEC 60529 for the measurement loop must be protected against envir...

Страница 9: ...for voltage problems such as a low loop power supply voltage or increased wiring resistance This also tests for other possible electrical part failures 5 Send a HART command e g via EDD DTM FDI simul...

Страница 10: ...guration parameters that are changed may affect the safety function of the device Therefore the safety function shall be checked again after modifications in accordance to the recommended proof tests...

Страница 11: ...mperature transmitter 1 15 2 01 00 For safety applications only these versions were considered Optional Display HMI Type AS Optional LCD Indicator display for TTH200 HMI Type BS Optional LCD Indicator...

Страница 12: ...actual number of field failures due to random events will be less than the number predicted by these failure rates The listed SN 29500 failure rates are valid for operating stress conditions typical o...

Страница 13: ...lt detection time is 2 minutes Only the current output 4 to 20 mA is used for safety applications Only one input and one output are part of the considered safety function The application program in th...

Страница 14: ...f data or information ABB Automation Products GmbH and its affiliates are not liable for damages and or losses related to such security breaches any unauthorized access interference intrusion leakage...

Страница 15: ...TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 15 14Appendix Exida FMEDA Report...

Страница 16: ...16 TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 14 Appendix Exida FMEDA Report...

Страница 17: ...TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 17...

Страница 18: ...18 TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 14 Appendix Exida FMEDA Report...

Страница 19: ...TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 19...

Страница 20: ...X200 SIL EN Rev E 07 2018 We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevai...

Отзывы: