TTH200, TTR200, TTF200 

 TEMPERATURE TRANSMITTER  |  SM/TTX200/SIL-EN REV. E 

1

 

Application area 

The TTH200, TTR200, TTF200 *H Series temperature transmitter are 2-wire 4 to 20 mA devices for the temperature monitoring of 
solids, fluids and gases of all types in containers and piping. 
Combined with a temperature sensor, the temperature transmitter become a temperature sensor assembly.  
The temperature sensors that can be connected to the temperature transmitters TT*200-*H for safety applications are: 

2-, 3- and 4-wire RTD 

Thermocouple 

The order variant ‘SIL2 - Declaration of Conformity’ meets the special SIL safety engineering requirements for the integration in 
Safety Instrumented Systems in compliance to 

IEC 61508 Edition 2 part 1 to part 7

The area of safety application is limited to: 

Up to SIL 2 as single transmitter installation

Up to SIL 3 as redundant transmitter installation

Mode of safety operation: Low Demand Mode

Hardware Fault Tolerance: HFT 0 (as single transmitter installation 1oo1)

Architectural Constraints: SIL 2 (based on Type B, HFT 0 and SFF 

â

 90%)

Systematic Capability: SC 3 according IEC 61508

The safety data, constraints, assumptions, installation / maintenance instructions and operating limits defined in the related 
documents needs to be considered.  
In case of questions and detected safety critical device failures please contact the 

ABB Customer service center

  

(Keywords: Product Type Designator, SIL). 

Customer service center 

Tel:   +49 180 5 222 580 
Mail:   [email protected] 

2

 

Purpose 

According IEC 61508-2 Annex D ‘Safety manual for compliant items’ the purpose of this safety manual is to document the information 
which is required to enable the integration of this item into a safety-related system in compliance with the requirements of the 
IEC 61508 standard.  

Содержание TTH200

Страница 1: ...ction TTH200 TTR200 TTF200 electronics for sensor head field and rail mounting for standard and high measurement This document must be considered in conjunction with related operating instructions Add...

Страница 2: ...afe Failure Fraction SFF 7 Average probability of dangerous failure on demand PFDAVG 7 6 Constraints 8 7 Periodic proof test and maintenance 9 Proof Test 9 8 Installation commissioning configuration 1...

Страница 3: ...2 as single transmitter installation Up to SIL 3 as redundant transmitter installation Mode of safety operation Low Demand Mode Hardware Fault Tolerance HFT 0 as single transmitter installation 1oo1 A...

Страница 4: ...of failure per unit of time usually declared as FIT DD detected dangerous failures DU detected dangerous failures SD detected safe failures SU intrinsic safe failures PFDavg Average probability of dan...

Страница 5: ...s High vibration environment The operation is above 67 maximum rating according to specification NAMUR NE43 Standardization of the signal level for the breakdown information of digital 4 to 20 mA tran...

Страница 6: ...range from 20 0 to 23 6 mA The factory setting is 22 mA The low alarm current can be configured in a range from 3 5 to 4 0 mA The factory setting is 3 6 mA In the following cases and by some electric...

Страница 7: ...Germany with results reported within FMEDA Report 12 04 016 TTx200 R023 Version V3 Revision R0 The summarized results are attached within Appendix Exida FMEDA Report Note The systematic safety integr...

Страница 8: ...even when the current output is active with the configured high alarm The head mounted electronics TTH200 with IP00 rating according IEC 60529 for the measurement loop must be protected against envir...

Страница 9: ...for voltage problems such as a low loop power supply voltage or increased wiring resistance This also tests for other possible electrical part failures 5 Send a HART command e g via EDD DTM FDI simul...

Страница 10: ...guration parameters that are changed may affect the safety function of the device Therefore the safety function shall be checked again after modifications in accordance to the recommended proof tests...

Страница 11: ...mperature transmitter 1 15 2 01 00 For safety applications only these versions were considered Optional Display HMI Type AS Optional LCD Indicator display for TTH200 HMI Type BS Optional LCD Indicator...

Страница 12: ...actual number of field failures due to random events will be less than the number predicted by these failure rates The listed SN 29500 failure rates are valid for operating stress conditions typical o...

Страница 13: ...lt detection time is 2 minutes Only the current output 4 to 20 mA is used for safety applications Only one input and one output are part of the considered safety function The application program in th...

Страница 14: ...f data or information ABB Automation Products GmbH and its affiliates are not liable for damages and or losses related to such security breaches any unauthorized access interference intrusion leakage...

Страница 15: ...TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 15 14Appendix Exida FMEDA Report...

Страница 16: ...16 TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 14 Appendix Exida FMEDA Report...

Страница 17: ...TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 17...

Страница 18: ...18 TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 14 Appendix Exida FMEDA Report...

Страница 19: ...TTH200 TTR200 TTF200 TEMPERATURE TRANSMITTER SM TTX200 SIL EN REV E 19...

Страница 20: ...X200 SIL EN Rev E 07 2018 We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevai...

Отзывы: