FIELD-MOUNT TEMPERATURE TRANSMITTER | CI/TTF300-EN REV. H
… 8 Commissioning
… Communication
Operating modes
• Point-to-point communication mode – standard (general
address 0)
• HART 5: Multidrop mode (addressing 1 to 15)
• HART 7: Addressing 0 to 63, independent of current loop
mode
• Burst Mode
Configuration options / tools
Driver-independent:
• HMI LCD indicator with configuration function
Driver-dependent:
• Device management / Asset management tools
• FDT technology – via TTX300-DTM driver
(Asset Vision Basic / DAT200)
• EDD – via TTX300 EDD driver
(Handheld terminal, Field Information Manager / FIM)
• FDI technology – via TTX300 FDI Device Package
(Field Information Manager / FIM)
Diagnosis notice
• Overrange- / underrange in accordance with NE 43
• HART® diagnosis
Extended from SW rev. 03.00:
• Device status signaling according to NE 107
• Freely configurable diagnostic categorization with
diagnostic history in accordance with NE 107
Tracking of events and configuration changes, from SW rev.
03.00
The HART® device stores information on critical events and
configuration changes.
The information can be output via tools:
• Event monitor for the logging of critical events
• Configuration monitor for configuration changes
For detailed information, see HART® COM/TTX300/HART
interface description.
PROFIBUS® Communication
Note
The PROFIBUS PA® protocol is an unsecured protocol, as such
the intended application should be assessed to ensure that
these protocols are suitable before implementation.
The interface conforms to Profile 3.01
(standard PROFIBUS®, EN 50170, DIN 1924 [PRO91]).
1
Transmitter
2
Bus termination
3
Segment coupler
4
PC / DCS
Figure 32: Example of PROFIBUS PA® interface connection
Manufacturer ID
0x1A
ID number
0x3470 [0x9700]
Profile
PA 3.01 (see PROFIBUS PA® interface
description (COM/TTX300/PB))
Configuration
On device using LCD indicator
DTM
EDD
GSD
Transmission signal
IEC 61158-2
Voltage / current consumption
• Average current consumption:12 mA.
In the event of an error, the FDE function (= Fault
Disconnection Electronic) integrated in the device makes
sure that the current consumption cannot exceed a
maximum of 20 mA.