33/62
TLE Series 160 to 500 UL S2B
UPS Installation Guide / REV-A
TLE Series 300 - 400 - 500 Access to the bus bars for the cable connections
Fig. 4.8-2 TLE Series 300 - 400 - 500 - Access to connection bus bars
To access Input, Output and Battery
connections proceed as follows:
•
Remove the front protection panel “
A
”.
•
Bottom entry cables: remove the plate “
B
”.
•
Top entry cables: remove the plate “
C
”.
Note!
For UPS correct operation, the input Utility
phase rotation must be clock-wise.
Please remove the plates “B and C” before
drilling any wholes
Note!
Panel “A, B and C” should never be removed or replaced with power applied to the UPS.
These panels are in close proximity to 480V live buss bars.
Always disconnect the Rectifier, Bypass, Load and Battery sources from the UPS before removing
or replacing these panels. If not serious injury or death could occur!
Q1
I ON
0
O
FF
A
B
C
Utility mains / Battery / Output load
Bottom entry cables
1
2
Top entry c
Utility input
Battery
Output load
Please remove
the plates (B & C) before
drilling any wholes
E
PO
E
PO
- +
TLES_UL_
300-500_
S2b_UPS c
onnection_
ABB_01US