2TLC172125M0201 Rev.F
14
10
Technical data
Further information about the product and accessories is found at:
new.abb.com/low-voltage/products/safety-products
Stated technical data apply when power supply voltage is +24 VDC and ambient temperature
is +25
°
C, unless stated otherwise.
Manufacturer
Address
ABB Electrification Sweden AB
SE-721 61 Västerås
Sweden
Order code/Ordering data
2TLA020054R0200: Tina 3A Adapter 2 contacts M12-5
2TLA020054R1400: Tina 3Aps Adapter 2 co
supply M12-5
Power supply
Required power supply type
PELV/SELV, not intended to be connected to a DC
distribution network.
Note:
A DC distribution network is defined in
IEC 61326-3-1:2017 as “Local DC electricity supply
network in the infrastructure of a certain site or
building intended for connection of any type of
equipment”.
Operating voltage
+24 VDC +15 %, -25 %
Total current consumption
Maximum: 35 mA
RMS
Note:
Total current consumption is the supply current when there is no information
output current, no current on Tina 3 Aps power output. Valid over the operating voltage
and ambient temperature range.
DYNlink signal
DYNlink Input signal voltage
Minimum: 8 V
RMS
Maximum: 15 V
RMS
DYNlink Output signal voltage
Minimum: 8 V
RMS
Maximum: 15 V
RMS
Note:
The purpose of stating the voltage in RMS is to facilitate the measurement of the
square-wave DYNlink signal with a multimeter.
Time delay between DYNlink
input and output signal (T
DELAY
)
Maximum: 70
µ
s
Information output
Output voltage high
low
Nominal: Operating voltage - 2 VDC
Maximum: 2 VDC
Output current
Maximum: 10 mA
Safety loop output
Current through safety device
contacts
Closed, nominal: 2 mA
RMS
Wetting, nominal: 12 mA for 700
µ
s after closing
contact
Short circuit current between
contacts
Nominal: 12 mA
Loop resistance
Closed, maximum: 500
Ω
Open, minimum: 20 k
Ω