Description of application and parameters
Application "Temperature"
Product manual 2CKA001473B9488
│143
11.6.1.2
Cycle time for sending of the actual temperature
Options:
Setting option from 00:00:25 to 01:30:00 (hh:mm:ss)
The actual temperature (room temperature) is sent on the bus cyclically.
The parameter is used to fix the time interval with which the measured room temperature is sent
to the linked RTC.
11.6.1.3
Temperature difference for sending within the cycle time *0.1 K
Options:
Setting option from 1 to 255
If the temperature increases rapidly within the set cycle time or falls, an additional sending of
the actual temperature can make sense.
The parameter can be used to set the change value from which the actual temperature is sent
during the cycle time (setting value x 0.1 Kelvin = ∆T).
Note
The cycle time for sending the actual temperature starts anew after the actual
temperature has been sent due to an exceeding of the set temperature
difference.
Note
The parameter is only adjustable if the "Send measured value" parameter is set
on "Cyclic and at value change".
11.6.1.4
Offset of the temperature sensor (x 0.1°C)
Options:
Setting option from -127 to 127
If the measured temperature is distorted by external influences or the device is mounted at a
location where it is always constantly being measured too much or too little, a compensation
value for the temperature measurement can be set.
The parameter is used to set the compensation value. The mounting location of the temperature
sensor and the suitable selection of the parameter settings are decisive for a good temperature
reading.