VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450
| CI/FSV/FSS/430/450-EN Rev. G 39
Analog input 4 ... 20 mA
(for FSx450 only)
External devices can be connected to the passive analog input
(4 ... 20 mA).
The function of the analog input can be selected via the
software ("Input/Output" menu).
The analog input can be configured via the "Easy Setup" menu
or the setup menu of the device. Before starting the
configuration, select the type of the connected signal and then
select the values for 4 mA and 20 mA that correspond to the
relevant output values of the connected device.
HART Input
The HART input can be configured via the "Easy Setup" menu
or the setup menu of the device. The device recognizes the
value and the corresponding unit via the HART input.
The remote transmitter must be operated in HART burst
mode.
If, for example, the pressure unit is set to psi in the setup
menu of the device but the pressure unit psi of the connected
pressure transmitter is set to kPa kPa, the VortexMaster /
SwirlMaster takes the pressure unit from the pressure
transmitter.
NOTICE
The use of the ABB pressure transmitters model 266 or
model 261 with the ordering option "P6 - HART Burst Mode"
is recommended.
DIP switch on the HART-communication board
Fig. 44: Communication board HART / 4 ... 20 mA
1
Interface for LCD indicator and service port
2
DIP switches
The communication board is located behind the front housing
cover. The LCD indicator may have to be removed to provide
access to the DIP switches.
The DIP switches are used to configure specific hardware
functions. The power supply to the transmitter must be briefly
interrupted in order for the modified setting to take effect.
The interface for the LCD indicator is also used as the service
port for device configuration.
DIP switch
Function
SW 1.1
Write protection switch
On: Write
protection
active
Off: Write
protection
deactivated
SW 1.2
Replacement mode (transfer system data)
On:
Replacement mode active
Off:
Replacement mode deactivated
SW 1.3
System data transfer direction
On:
Transmitter -> sensor
Off:
Sensor -> transmitter
SW 1.4
Selection whether the alarm function is configured via
software or DIP switch.
On:
Selection of alarm current via SW 1.5
Off:
Selection of alarm current via the "Input/Output /
Iout at Alarm" menu.
SW 1.5
Selection of alarm current
On:
Low alarm (3.5 ... 3.6 mA)
Off:
High alarm (21.0 ... 22.6 mA)
SW 1.6
Format SensorMemory
Service function! - Risk of data loss in the device.
Write protection switch
When write protection is activated, device parameterization
cannot be changed via HART or the LCD indicator. Activating
and sealing the write protection switch protects the device
against tampering
Downloading system data, replacing the transmitter
When replacing transmitter components (communication
board), system data must be downloaded from the
SensorMemory.
Download of system data and the system data transfer
direction is activated using DIP switches SW 1.2 and SW 1.3.
See chapter "Repair“ in the operating manual.
Status of the current output
DIP switches SW 1.4 and SW 1.5 can be used to configure
the status of the current output in the event of an alarm /
error.
If the current in the event of an alarm is selected via DIP
switch SW 1.5, the setting can no longer be changed using
HART or the LCD indicator.
G11840
COMMUNICATION PROTOCOL
SW1.1
SW1.2
SW1.3
Data access
right
Replace
mode
Replace
direction
0:Read only
1:Read/write
0:Enable
1:Disable
0:CB to FE
1:FE to CB
SW1.4
SW1.5
SW1.6
CO alarm
mode
NV format
0:pin SW1.5
1:software
0:Low
1:High
0:Enable
1:Disable
CO alarm mo-
de selection
1
2
3
4
5
6
1