ABB i-bus
KNX
Device technology
SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 17
2.2.4
Operating and display elements
Operation/
Indicator light
Description
Function
LED green
Indicates status of mains and output
voltage
The LED is off during programming.
ON:
Mains voltage present, device operating normally
(I < I
Ovl
)
OFF:
Mains voltage absent
LED red
Indicates overload/short-circuit current.
The LED lights up when the output
current exceeds the overload limit
(I > I
Ovl
). For SV/S 30.640.5.1, overload
and short-circuit current values apply to
the total current, I = I
1
+ I
2
SV/S 30.320.2.1
SV/S 30.640.5.1
ON (I > I
Ovl
)
I > 500 mA
I > 900 mA
7 LEDs (yellow)
LED No.:
7.
6.
5.
4.
3.
2.
1.
Indicates present bus current
If a current value exceeds/falls below
the indicator value by +/-
5 % for at
least 110 ms, the LED comes ON/goes
OFF.
Example, SV/S 30.640.5.1:
LED No. 2 (200 mA) lights up if the
output current exceeds/stays at
210 mA for 110 ms. The LED goes off
if the current falls below 190 mA for at
least 110 ms.
LED
No.:
SV/S 30.320.2.1
SV/S 30.640.5.1
Indicator value
[mA]
Indicator value
[mA]
7.
350
700
6.
300
600
5.
250
550
4.
200
400
3.
150
300
2.
100
200
1.
50
100
Triggers and indicates a bus reset.
This function can be triggered only
when mains voltage is applied.
Operating one line with two power
supplies:
when the mains supply fails, the Reset
button on the affected device does not
function.
Reset button: Pressing the button for > 2 seconds triggers a
reset. The line shorts. Pressing the button again
during a reset has no effect (no reaction, no
retrigger, no interrupt, etc.)
ON:
After pressing for > 2 secs. or for the duration of
the reset (20 s) after receiving the object value.
ON:
After 20 s reset
Flashes:
At 4.8 Hz while being pressed
Indicates a KNX telegram
AN:
Receiving telegram
OFF:
Stand-by mode
Indicates a communication error on the
bus
ON:
The LED comes ON for 1 second and is
retriggerable if there is a transmission error or if a
telegram fails or is incomplete (e.g. “BUSY”,
“NAK” (receipt not correct)).
OFF:
Device working normally
Please note
Individual LEDs may flash during downloads or while the application is being unloaded.