24
Measured value
Code
Data direction
Value
Number of starts, stage 1
V1
R
0...255
Number of starts, stage 2
V2
R
0...255
Number of starts, stage 3
V3
R
0...255
Number of starts, stage 4
V4
R
0...255
Number of trips, stage 1
V5
R
0...255
Number of trips, stage 2
V6
R
0...255
Number of trips, stage 3
V7
R
0...255
Number of trips, stage 4
V8
R
0...255
Number of recovery operations
V9
R
0...255
Red operation code of display
V10
R
0...10
Minimum df/dt measured
V60
R
0.0...-10.0 Hz/s
Minimum frequency measured
V61
R
20.00...75.00 Hz
Maximum df/dt measured
V62
R
0.0...10.0 Hz/s
Maximum frequency measured
V63
R
20.00...75.00 Hz
The parameters V11...V54 can be used to read
(R) the five latest values recorded. Event n is
the most recent value recorded, event n-1 the
previous value, and so on.
Recorded data
Event
Measuring range
n
n-1
n-2
n-3
n-4
Voltage U
V11
V21
V31
V41
V51
0.0...1.4 x U
n
Frequency f
V12
V22
V32
V42
V52
20.00...75.00 Hz
Frequency rate of change
l
Idf/dtI
l
V13
V23
V33
V43
V53
0.0...
±
10.0 Hz/s
No. of tripped stage and output
V14
V24
V34
V44
V54
0, 11, 12, 21,22,
31, 32, 41, 42 *)
*) 11 to be understood as stage 1 timer t
1
, 32 as stage 3 timer t
3'
, etc.
Measured and
recorded parameter
values
Содержание SPAF 140 C
Страница 14: ......