21
Blocking input, CHANNEL 8
Terminal numbers
X2/6-7
Input voltage range
- input module type SPTR 2B17
80…265V dc
- input module type SPTR 2B18
30…80 V dc
Current consumption at activation
<2 mA
Output contacts
CB control output terminals
X0/66-97, 65-96 and 86-99, 85-98
Rated voltage
250 V ac or dc
Continuous carry
5 A
Make and carry for 0.5 s
30 A
Make and carry for 3 s
15 A
Breaking capacity for dc, when the control circuit
time constant L/R
≤
40 ms at the control voltage
levels 48/110/220 V dc
5 A/3 A/1 A
Contact surface material
AgCdO
2
Control output operating mode,
when operated by the control module
pulse shaping
- control pulse length
0.1…100 s
Signalling output terminals
X1/1-2-3, 4-5, 6-7, 8-9 and 10-11
Rated voltage
250 V ac or dc
Continuous carry
5 A
Make and carry for 0.5 s
10 A
Make and carry for 3 s
8 A
Breaking capacity for dc, when the control circuit
time constant L/R
≤
40 ms at the control voltage
levels 48/110/220 V dc
1 A/0.25 A/0.15 A
Contact surface material
AgCdO
2
Auxiliary supply voltage
Type of power supply module and corresponding
supply voltage range
- type SPGU 240A1
80...265 V ac or dc
- type SPGU 48B2
18...80 V dc
operating conditions
~10 W / ~15 W