18
S M A RTR ACK ™ M V
R EM OT E R AC K I N G D E V I C E
—
Specifications
Parameter
Value
Mechanical Life
500 Operations
Ambient Temperature Range
0°C to +40 °C
Continuous Output Torque
35 ft-lbs
Racking time from
Disconnect to Connect
<120 seconds
Weight
25-50 lbs
Power Cable Length
25 feet
Control Cable Length
25 feet
Power Cable Size
10 gauge
Parameter
Value
Input Voltage
120 VAC
Rated Current
<20 Amps
Environmental
This is indoor equipment and is designed to operate
under standard service conditions as defined in ANSI
C37.04 for breakers and C37.20.2 for the switchgear
assembly washer that need to be removed from the
center of the lever itself. Then there are two screws
that hold the position release stop onto the door. Both
the position release stop and position release lever
need to be removed and discarded.
—
Table 4: Mechanical
—
Table 5: Electrical