SM500F
Field mountable paperless recorder
8 Specification
144
IM/SM500F Rev. Z
Logic Equations (optional)
Number
8
Size
11 elements each
Functions
AND, OR, NAND, NOR, XOR, NOT
Tags
20-character tag for each equation
Update rate
300 ms
EMC
Emissions & immunity
Meets requirements of IEC61326 for an Industrial Environment
Electrical
Supply ranges
100 V to 240 V AC ± 10% (90 V min. to 264 V max.) or
105 V DC min. to 115 V DC max.
10 V to 36 V DC (optional)
Power consumption
10 W max.15 VA max.
Power interruption protection
No effect for interrupts of up to 20 ms
Safety
General safety
EN61010-1
Overvoltage Class III on mains, Class II on inputs and outputs
Pollution category 2
CSA 61010-1
UL 61010-1
Isolation
500 V DC to earth (ground)