40
2TLC010073M0201 Rev.G
Power supply
Internal consumption
6W
Required fuse
4 A gG external fuse is required (According to
UL248: any (JDYX/7) Fast acting,Ratings 250V,
4A, IR200A)
Relay output specification
Relay output configuration
Note 1
2 NO + 2 NO Note 1
Maximum operating switching voltage
250 VAC
Overvoltage category
II
Rated impulse withstand voltage
4 kV
Rated operational voltage
250 VAC
Minimum operating contact load
5 VDC / 10 mA (15 VDC / 3 mA)
Maximum operating switching frequency
0.5 Hz
Rated isolation voltage
400 V
Note 1
: Two relay groups. The second relay group can be controlled with timer settings.
Note!
In a 400 V system a 3 phase load shall only be used in a star connection.
NO contact
AC load (AC15, AC1)
Rated operating voltage (Ue)
250 VAC
Rated operating current (Ie)
1 contact
3A
2 contacts
3A
3 contacts
3A
4 contacts
3A
DC load (DC13, DC1)
Rated operating voltage (Ue)
+24 VDC
Rated operating current (Ie)
1 contact
3A
2 contacts
3A
3 contacts
3A
4 contacts
3A
Required fuse
4 A gG, >=1 kA short circuit protection (4 A according to
UL248)
T1/T2 safety device interface specification
Output (O) T1 and T2
Output high voltage (VOH)
Note 1
Minimum
15.8 VDC
Maximum
25.6 VDC
Maximum output low voltage (VOL
max
)
0.8 VDC
Maximum output current
Note 2
50 mA
Signal frequency
5 Hz ±1 Hz
Pulse length
500 μs ±100 μs
Square wave signal frequency
217 Hz ±3 Hz
Maximum capacitance to ground
100 nF
Note 1
: VOH typical = power supply voltage -2.8 VDC
Note 2
: Current limited internally to typical 70 mA