24
2TLC010062M0201 Rev.F
Note!
BSR23 is supplied with power through its signal input port R.
Relay output specification
Relay output configuration
4 NO + 1 NC
Maximum operating switching voltage
Note
250 VAC
Overvoltage category
II
Rated impulse withstand voltage
4 kV
Rated operational voltage
250 VAC
Minimum operating contact load
5 VDC / 10 mA (15 VDC / 3 mA)
Maximum operating switching frequency
0.5 Hz
Rated isolation voltage
400 V
Note!
In a 400 V system a 3 phase load shall only be used in a star connection.
NO contact
AC load (AC15, AC1)
Rated operating voltage (Ue)
250 VAC
Rated operating current (Ie)
1 contact
5A
2 contacts
5A
3 contacts
4.6A
4 contacts
4A
DC load (DC13, DC1)
Rated operating voltage (Ue)
+24 VDC
Rated operating current (Ie)
1 contact
6A
2 contacts
5.6A
3 contacts
4.6A
4 contacts
4A
Required fuse
6.3 A gG, >=1 kA short circuit protection (6 A according to
UL248)
NC contact
AC load (AC15, AC1)
Rated operational voltage (Ue) 250 VAC
Rated operational current (Ie) 0.5A
DC load (DC13, DC1)
Rated operational voltage (Ue) +24 VDC
Rated operational current (Ie) 2A
Required fuse
4 A gG (4 A according to UL 248)
Safety device interface specification
Input (I) R1 and R2
Maximum operating input voltage
27.6 VDC
Minimum input high voltage (VIH
min
)
Note 1
19.2 VDC
Maximum input low voltage (VIL
max
)
Note 2
2 VDC
Typical input impedance
1.5 kΩ
Maximum current sink (I
sink
)
70 mA
Note 1
: Voltage level above VIH
min
is interpreted as logic “1”, in worst case operating
conditions.
Note 2
: Voltage level below VIL
max
is interpreted as logic “0”, in worst case operating
conditions.
Test/start/reset interface specification
Input (I) X1/X2