Parameterization
CI/FMT400-VTS/VTCS-X1
Sensyflow FMT400-VTS, FMT400-VTCS
EN - 25
7 Parameterization
The configuration of the mass flowmeter can be changed with the aid of an LCI (local
communication interface) adapter that has to be connected to the parameterization socket.
This adapter is available as a separate accessory and comes supplied together with the
relevant software.
The following parameters can be modified or read in:
Read device data
Show current settings
Measurement range
Selection within the calibrated measurement range
Low flow
Low flow suppression 0...20 % of the upper range limit
Filter factor
Attenuation, 1 ... 500 can be selected (default: 50)
Output in the event of an error Minimum (lower than 3.5 mA) or maximum (greater than 22.5 mA)
Analog output
0 / 4 ... 20 mA
Save modified data
Save settings
Factory setting
Select default setting
Status Check
function
Reset Restart
Print out
Print out current settings
Password
For service technicians only
To activate the configuration changes, the device must be restarted. To do so, use the
command "restart reset" or briefly interrupt the power supply for approximately 10 seconds.
8 Error
messages
If failures occur (e.g., sensor wire break), the 0/4 ... 20 mA output will adopt the configured
control value.
In the event of an error, the following settings can be made:
- Minimum
< 3.5 mA
- Maximum
> 22.5 mA
IMPORTANT (NOTE)
Default preset in case of a fault
Maximum
0 ... 20 mA
Minimum
4 ... 20 mA
These settings can be modified using the LC interface and the corresponding configuration
software.
Other error messages can be read out via the "status" function ("check function", section 7).