background image

SC, SC-1, SV and SV-1 Relay

I.L. 41-766.1N

3

with tapped coils, as there is not sufficient space for
marking a scale for each tap. However, the scale
plate is supplied in order that a customer may mark
on it the individual relay setting or settings if desired.

3.0

INSTALLATION

The relays should be mounted on switchboard pan-
els or their equivalent in a location free from dirt,
moisture, excessive vibration, and heat. Mount the
relay vertically by means of the four mounting holes
on the flange for semi-flush or by means of the rear
mounting stud or studs for projection mounting.
Either a mounting stud or the mounting screws may
be utilized for grounding the relay. The electrical con-
nections may be made directly to the terminals by
means of screws for steel panel mounting or to the
terminal studs furnished with the relay for thick panel
mounting. The terminal studs may be easily removed
or inserted by locking two nuts on the stud and then
turning the proper nut with a wrench.

For detailed FT case information refer to I.L. 41-076.

4.0

ADJUSTMENTS AND MAINTE-
NANCE

The proper adjustments to insure correct operation of
this relay have been made at the factory and should
not be disturbed after receipt by the customer.

 If the

adjustments have been changed, the relay taken
apart for repairs, or if it is desired to check the adjust-
ments at regular maintenance periods, the instruc-
tions below should be followed.

All contacts should be cleaned periodically. A contact
burnisher Style 182A836H01 is recommended for
this purpose. The use of abrasive material for clean-
ing contacts is not recommended, because of the
danger of embedding small particles in the face of
the soft silver and thus impairing the contact.

Several factors may affect the dropout ratio of the
relay. Whatever affects the ratio does so because
either the dropout or pickup or both are affected.
Obviously, incorrect assembly or interchange of
parts, such as the use of the SC plunger with the SV
core tube, will alter the electrical characteristics.
However, the factor most likely to be encountered in
service is friction. This may be due to dirt or foreign
material between the plunger shaft and its bearings,

to excessive pressure of the indicator screen on the
indicator, or to leads so mis-shaped that they tend to
rotate or tilt the moving contact insulation plate with
appreciable force.

In order to remove the plunger and shaft assembly, it
is necessary to remove the setscrew and nut at the
top of the shaft. The spool-shaped bushing assem-
bled on the upper end of the plunger shaft has a por-
tion of its center section machined off so that the
shaft is exposed at this point and can be prevented
from turning by gripping shaft and bushing with a pair
of long-nose pliers while removing the set screw and
nut. Then by pressing down with the fingers on the
upper end of the shaft, the lower split sleeve which
retains the lower bearing will be forced out of the
threaded tube, the bearing will drop out freely, and
the upper split sleeve will be forced out far enough to
permit grasping it for removal. The shaft and plunger
assembly then can be removed.

The shaft and plunger assembly should be handled
carefully to avoid bending the shaft or damaging the
bearing surfaces.

 The shaft should never be gripped

on it upper bearing surface, below the spool-shaped
bushing

, when loosening the nut and setscrew, as

this would almost certainly damage the bearing sur-
face. The shaft bearing surfaces should not be
cleaned or polished with any abrasive material, as
the abrasive particles might become imbedded in the
shaft and cause difficulty later. The plunger shaft and
bearings may be cleaned by wiping them carefully
with a clean, lint-less cloth. Use no lubricant on the
plunger shaft or bearings when re-assembling the
relay, since this will eventually become gummy and
prevent proper operation. It is recommended that the
shaft be cleaned at intervals of approximately two
years. When replacing the lower bearing and the split
sleeves, the shorter sleeve (assembled below the
bearing) should be pushed in until it is flush with the
end of the threaded tube.

The mounting holes in the operation indicator screen
are slotted so that its position can be adjusted. For
relays in which the moving contacts are not latched
in the operated position, the screen should be so
located that the indicator positively enters the screen
opening when the contacts barely touch. For latch-
type relays, the screen should be so located that
good contact is still obtained when the relay is de-

Содержание SC

Страница 1: ... pickup 35 to 60 for the ac relays The SV should not be used if the normal applied voltage is in the vicinity of pickup plus or minus 10 The SC may be used in fault detector applications where direct energization of a breaker trip coil is involved It should not be used to energize a timer The SV should be used only in overvoltage applica tions 2 0 CONSTRUCTION The types SC SC 1 and SV and SV 1 rel...

Страница 2: ... on slotted brackets These are held in position on the base by filister head screws which are threaded into the ter minal inserts Lockwashers are assembled inside the molded terminal bushings between the inserts and the base as a safeguard against loosening of the screws By rotating the bracket on its mounting screw and moving it along its slot the contact assembly can be made either normally open...

Страница 3: ...s bearings to excessive pressure of the indicator screen on the indicator or to leads so mis shaped that they tend to rotate or tilt the moving contact insulation plate with appreciable force In order to remove the plunger and shaft assembly it is necessary to remove the setscrew and nut at the top of the shaft The spool shaped bushing assem bled on the upper end of the plunger shaft has a por tio...

Страница 4: ... trials the plate comes to rest with the center line of the contacts approximately parallel to the base and with its mounting hole fairly well centered with the end of the shaft if the plate does not tip appreciably and if the leads have a safe clearance to the stationary contact brackets the leads are properly shaped If this check shows that re shaping is necessary it may be possible to obtain su...

Страница 5: ...SC SC 1 SV and SV 1 Relay I L 41 766 1N 5 THIS SPACE RESERVED FOR NOTES ...

Страница 6: ...25 40 40 10 15 20 99 28 6 9 1 5 24 07 03 1 7 0 6 0 18 225 65 19 5 7 16 05 5 1 0 2 85 98 85 98 85 98 85 98 85 98 85 98 85 98 85 98 65 80 65 80 65 80 65 80 65 80 65 80 65 80 65 80 SC 1 SC 1 SC 1 SC 1 SC 1 SC 1 SC 1 SC 1 DC 25 to 60 Hz DC 25 to 60 Hz DC 25 to 60 Hz DC 25 to 60 Hz DC 25 to 60 Hz DC 25 to 60 Hz DC 25 to 60 Hz DC 25 to 60 Hz 5 2 1 4 2 8 4 16 10 40 20 80 40 160 4 100 1 5 3 6 12 25 40 40 ...

Страница 7: ... SC 1 relays at 3 10 and 20 times minimum pickup current are approximately 31 240 and 770 V A respectively Dropout ratio varies somewhat with pickup adjustment but will be approximately constant for any given pickup setting Limits in tables include variables such as friction and other individual relay variations Maximum continuous volts given for the SV and SV 1 relays for ac are for the relay set...

Страница 8: ...contact leads Sub 4 182A854 Figure 2 Internal Schematic of the Single Unit Type SC or SC 1 Relay in the Type FT 21 Case Sub 4 182A855 Sub 1 182A856 Figure 3 Internal Schematic of the Double Unit Type SC or SC 1 Relay in the Type FT 21 Case Figure 4 Internal Schematic of the Single Unit Type SV or SV 1 Relay in the Type FT 21 Case ...

Страница 9: ...Make or Break As Required Bottom Unit Top RH Unit Front View Top LH Unit Front View Chassis Operated Shorting Switch Test Switch Current Test Jack Terminal Note Coils tapped for 1 to 25 Ratio Range when used Figure 5 Internal Wiring of the Relays in the Small Glass Case Figure 6 Internal Schematic of the Single Unit Type SC or SC 1 Relay in the Type FT 21 Case Figure 7 Internal Schematic of the Do...

Страница 10: ...I L 41 766 1N SC SC 1 SV and SV 1 Relay 10 Figure 9 Internal Schematic for Relays in Front Connected Case Sub 5 184A942 ...

Страница 11: ...SC SC 1 SV and SV 1 Relay I L 41 766 1N 11 Figure 10 Typical Time Curves for the Types SC and SV Relays Using Flux Shunt for Pickup Adjustment Sub 1 143285 ...

Страница 12: ...I L 41 766 1N SC SC 1 SV and SV 1 Relay 12 Figure 11 Typical SC SC 1 Current Relays dc or 25 to 60 Hertz Sub 1 471008 ...

Страница 13: ...SC SC 1 SV and SV 1 Relay I L 41 766 1N 13 Figure 12 Pickup on Variable Frequency for SC SC 1 Current Relays Sub 1 471013 ...

Страница 14: ...I L 41 766 1N SC SC 1 SV and SV 1 Relay 14 Figure 13 Typical Type SV Voltage Relay 120 Volts 60 Hertz Range 70 to 150 Volts Sub 1 471009 ...

Страница 15: ...SC SC 1 SV and SV 1 Relay I L 41 766 1N 15 Figure 14 Pickup on Variable Frequency for SV Relay 120 volts 60 Hertz Set at 70 volts Sub 1 471020 ...

Страница 16: ...I L 41 766 1N SC SC 1 SV and SV 1 Relay 16 Figure 15 Outline and Drilling Plan for Single Unit Relays in small glass projection case Sub 6 77D418 ...

Страница 17: ...SC SC 1 SV and SV 1 Relay I L 41 766 1N 17 Figure 16 Outline and Drilling Plan for Relays in Front Connected Case Sub 5 188A098 ...

Страница 18: ...I L 41 766 1N SC SC 1 SV and SV 1 Relay 18 Figure 17 Outline and Drilling Plan for Single and Double Unit Relays in the Type FT 21 Case Sub 17 57D7901 ...

Страница 19: ...SC SC 1 SV and SV 1 Relay I L 41 766 1N 19 Figure 18 Outline and Drilling Plan for Three Unit Relays in Type FT 32 Case Sub 17 57D7903 ...

Страница 20: ...766 1N SC SC 1 SV and SV 1 Relay Printed in U S A ABB Automation Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd ABB ABB ABB ABB ...

Отзывы: