Section 2
1MRK 511 434-UEN A
SAM600 Process Bus I/O System
18
SAM600 Process Bus I/O System
Operation Manual
shows an example configuration. The SAM600 system consists of four
SAM600 modules. Based on the configuration applied, the necessary services are
enabled on the related ports. Not configured ports are automatically closed by the
configuration.
Figure 7: Example configuration
Depending on the position of the SAM600 module in the SAM600 system, each
SAM600 module is assigned with one or two ports to the SAM600 system bus
communication. This also applies when the SAM600 system consists of only one
SAM600 module.
Figure 8: SAM600 System configured for redundant communication
SAM600
VT
SAM600
CT
SAM600
TS
SAM600
TS
Process Bus
(single link, electrical)
9-2LE bridge through
Process Bus
(single link, optical)
9-2LE bridgie through
Redundant SAM600 System Bus
Process Bus to PRP LAN-A
Process Bus to PRP LAN-B
Process Bus HSR
(optional with IEEE time
synchronization)
X101
X104
X103
X104
X102
X101
X106
X107
X101
X102
X103
X104
X104
X101
Kiosk
Kiosk
(optional with IEEE 1588 time
synchronization)