4.4
Instantiating a SAM600 system
4.4.1
Configuration wizard
GUID-439EB87E-1674-499B-B295-740EE885C5A2 v1
Depending on the installed Connectivity Package, the context menu or the Object Types view
shows the possible available SAM600 systems to insert on the bay level Plant Structure, see
.
On the bay level Plant Structure it is possible to insert a SAM600 system in online or offline
mode.
•
Online mode: When a SAM600 system is connected to PCM600 and the communication is
established, PCM600 reads the configuration from the physical SAM600 system. PCM600
reads hardware modules, serial numbers, access points, and SAM600 system information
from a SAM600 system
•
Offline mode: When the physical SAM600 system is not available or not connected to
PCM600, the engineering steps are done without any synchronization with a SAM600
system. The offline configuration in PCM600 is synchronized with the physical SAM600
system at a later state by connecting a SAM600 system to PCM600 and downloading the
configuration
The green check mark next to a SAM600 icon in
communication between a SAM600 system object in PCM600 and the
physical SAM600 system is established.
IEC18000107 V1 EN-US
Figure 4:
Plant structure with online SAM600 system
•
Import a template into a SAM600 system available in the template library as a *.pcmt file.
•
Import a pre-configured SAM600 system configuration available as a *.pcmi file.
The detailed instructions are found in the PCM600 online help.
4.5
Inserting an SAM600 system in online mode
GUID-8D383D3B-5078-48FC-B16D-AD24B978798F v1
Follow the procedure to insert an SAM600 system in online mode:
1.
Right-click on the Bay, navigate to New and select SAM600 MU application type.
2.
Select and click a SAM600MU, see
. A SAM600 MU Configuration Wizard dialog
box appears.
1MRK 511 433-UEN B
Section 4
Setting up a project
SAM600 Process Bus I/O System
13
Engineering manual