ABB | SACE Tmax XT
132 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
External accessories | 4 - Ekip Com Modbus RTU
4 - Ekip Com Modbus RTU
Ekip Com Modbus RTU
is a communication accessory which allows Ekip Touch to be integrated into an RS-
485 network with Modbus RTU communication protocol, remote supervision and monitoring functions, in two
different modes, master and slave.
You can perform the following operations remotely:
• read Ekip Touch measurements and information
• manage certain controls, including opening and closing the actuator (MOE-E)
• access information and parameters not available on the display
• If connected to a withdrawable version of the circuit-breaker, the allows the racked-in/racked-out status
to be detected
NOTE:
the remote open and close commands of the circuit-breaker can only be executed if
Ekip Touch is in the Remote configuration
The System Interface document is available for mapping the module in its communication network. All the
required communication and command details are listed in the document (page 129).
Accessories
Ekip Cartridge
and
Ekip Supply
are required in order to connect
Ekip Modbus RTU
to Ekip Touch
Models
Two different modules compatible with the Modbus RTU protocol are available:
Ekip Com Modbus RTU
and
Ekip Com Modbus RTU Redundant
.
The modules are identical in terms of characteristics and installation methods, except for: display menus,
cabling and addresses for system communication, which are specific for each module.
NOTE:
if different indications are not given, the information in the next chapter is valid for
both models
The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the unit
(e.g. for applications where high grid reliability is required).
IMPORTANT: each Ekip Touch can be fitted with only one module per type. The
configuration with two modules of the same model is not allowed (example: two Ekip
Com Modbus RTU Redundant)
Connections
To connect the module to its communication network and for references about the terminals, please consult
document
; use Belden 3105A type cables or equivalent for the external cabling.
To connect the module to
Ekip Supply
and
Ekip Cartridge
, please consult documentTo connect the module
to Ekip Touch, please consult document
.
Power supply
Ekip Com Modbus RTU
is supplied directly by the
Ekip Supply
module to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Содержание SACE Tmax XT5
Страница 2: ...ABB SACE Tmax XT 2 2019 ABB 1SDH002039A1002 ECN000093027 Rev A ...
Страница 4: ...II 2019 ABB SACE Tmax XT 1SDH002039A1002 ECN000093027 Rev A ...
Страница 204: ...ABB SACE Tmax XT 202 2019 ABB 1SDH002039A1002 ECN000093027 Rev A Other accessories 5 Testing and Programming ...
Страница 205: ...1SDH002039A1002 ECN000093027 Rev A ...